background image

 

MAP1 

Page 22 of 31 

 

Installation Manual 

June 2018 • Rev. 1.6 

 

POWER CONNECTOR 

 

 

 
Connections

:  

 

 

METBA and METBB are for future use. The Shield from METBA and METBB 
wire would be connected to METTAM.  

 

TAMPER allows for the connection of an external Enclosure Tamper Switch.  
 

Note

The MAP1 has a Tamper MSJx-MicroShunt jumper to the right of this power 

connector.  

 

 

Figure 13

 

Factory default

:  

The Tamper jumper 
is set to disabled.  

To activate the 
Panel Tamper move 
jumper to the right 
2 pins. Connect the 
switch between 
TAMPER and the 
METTAM on the 
connector. 

Figure 14

 

Содержание MAP1

Страница 1: ...MAP1 Controller INSTALLATION MANUAL June 2018...

Страница 2: ...act Wiring 12 Lock Output and Multi Function Relay Wiring 15 Input and Output Point Wiring 17 Appendix 20 MAP1 System Indicators 21 Power Connector 22 PB1 Shutdown Button 23 PB2 IP Reset Button and St...

Страница 3: ...e and data cannot be shared between modes Input and Output points are available when not used on a provisioned door Note I O points may be available in future release of Webster and Cloud Lock The MAP...

Страница 4: ...Relays All Relays 8 per panel Form C SPDT 6 A 30 VDC Inputs per Provisioned Doors Supervised or Non Supervised Door Contact 2 per MAP1 Requires normally closed contact On Off door switch Exit Button 2...

Страница 5: ...MAP1 Page 5 of 31 Installation Manual June 2018 Rev 1 6 Note Specifications subject to change without notice...

Страница 6: ...rgency lockdown functions which are dependant in any way on the operation of card readers access control panels communications networks communications devices or host software Wiring Note Improper Wie...

Страница 7: ...MAP1 Page 7 of 31 Installation Manual June 2018 Rev 1 6 MAP1 Controller Layout Figure 1...

Страница 8: ...input and output points a 2 door configuration 2 lock relays 2 multi function relays 2 REX RTE 2 door contacts DPS 4 input points and 4 output points OR b 4 door configuration 4 lock relays 4 multi fu...

Страница 9: ...static IP address or reset if necessary See Appendix section for more information Mechanical Information 1 The MAP1 has 2 horizontal mounting flanges which should be used to attach the product to a s...

Страница 10: ...t effective to use a separate power supply battery backed up just for the MAP1 Controller and a separate power supply which can be sized to supply the amount of current that the attached high current...

Страница 11: ...ional exit reader wiring diagram proceed to the next section READER LED ON Reader Active Two Inputs and two Outputs are used for RTE REX door contacts well as lock relays and multi function relays res...

Страница 12: ...s highly recommended that the MAP1 be removed from the attached surface to do a change of the MSJx position See figure 6 below Reader 1 uses Input 1 Door Contact DPS and Input 2 RTE REX Reader 2 uses...

Страница 13: ...MAP1 Page 13 of 31 Installation Manual June 2018 Rev 1 6 Figure 6 Non Supervised...

Страница 14: ...MAP1 Page 14 of 31 Installation Manual June 2018 Rev 1 6 Figure 7 Supervised...

Страница 15: ...This relay can be set to only one of the following options Alarm Shunt factory default Shunt the alarm system before opening lock Door Held Open Door has been left open Forced Entry Door opened withou...

Страница 16: ...iction to verify the specific requirements Also a building permit may be required in some jurisdictions for the installation of magnetic locks Figure 9 See Note 2 in Appendix section for 6 Amp relay r...

Страница 17: ...MAP1 Page 17 of 31 Installation Manual June 2018 Rev 1 6 INPUT AND OUTPUT POINT WIRING General Layout Figure 10...

Страница 18: ...etting is non supervised Supervised input points require a Cansec CA EOL resistor pack to be placed at the device being monitored Supervised input points will inform the host of 4 supervised states Al...

Страница 19: ...n moving the MSJx MicroShunt jumpers small and easily dropped accuracy is important during movement it is advisable to set up the MAP1 Controller prior to attaching it to a surface It is highly recomm...

Страница 20: ...batteries 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm 6 65 lbs 3 02 kg 12 24 VDC selectable output 6 Amp Enclosure Style Power Supply with Backup Battery Charger Eight individual Class 2 rated power...

Страница 21: ...s 1 beep after powered up PM1 LED ON PM2 LED OFF Webster Mode Mode indicator MAP1 emits 2 beeps after powered up PM1 LED ON PM2 LED OFF Cloud Lock Mode Mode indicator MAP1 emits 3 beeps after powered...

Страница 22: ...ted to METTAM TAMPER allows for the connection of an external Enclosure Tamper Switch Note The MAP1 has a Tamper MSJx MicroShunt jumper to the right of this power connector Figure 13 Factory default T...

Страница 23: ...wn This will take 15 to 20 seconds 3 Wait untill all LEDs except power are turned off by the system Then remove the Power Connector 4 If the Shutdown does not occur try the procedure again If it still...

Страница 24: ...LEDs and at the end it will emit a series of beeps to indicate its mode e g First Access Cloud Lock or Webster 3 Plug the MAP1 to the network with a DHCP server available 4 Install and launch MAP1 IP...

Страница 25: ...t with IT personnel and enter the IP address Subnet Mask Gateway IP Address and Port numbers Note The optional Trusted Host IP see Figure 18 instructs the panel to accept data connection only from the...

Страница 26: ...tings and reboots for the settings to take effect USB IP CONFIGURATION TOOL Important Shutdown Push Button PB1 must be used to avoid data corruption on the MAP1 controller 1 If the MAP1 controller is...

Страница 27: ...er up sequence which takes about 30 to 40 seconds When complete the MAP1 controller will emit a series of beeps to indicate its mode e g First Access Cloud Lock or Webster 6 Remove the USB flash drive...

Страница 28: ...puter is connected to SrvPort 5000 Factory default server port You may change it or leave it as default DiagPort 5001 Factory default diagnostic port You may change it or leave it as default UpdatePor...

Страница 29: ...Remove the line USB INIT DONE and save the file before removing it from your computer 10 Repeat from step 1 to step 6 then proceed to step 11 11 Insert the flash drive into a USB port on a computer Wh...

Страница 30: ...button event A message will be transmitted to the host software if the panel is online DOOR HELD OPEN OUTPUT The MF multifunction relay when configured as Door Held Open will be activated if the lock...

Страница 31: ...ollowed by a one second pulse on this MF relay which is used to trigger the door operator DOOR OPERATOR OUTPUT HANDICAP CARDS ONLY The MF multifunction relay when configured as Door Operator_HC will o...

Отзывы: