CP40
Page 24 of 43
Installation Manual
October 2015 • Rev. 2.7
Exit Button and Door Contact Wiring
DOOR CONTACTS
To monitor forced-entry or door-held-open
alarm conditions, connect normally closed
door contacts to the door contact inputs.
Door contact inputs must be enabled via the following jumpers:
.
To enable door contact set a jumper to the right side of the board (right
two pins)
EXIT BUTTONS
Connect a normally open momentary switch to each exit button input.
Exit buttons must be enabled through the
Reader Type
DIP Switch (S5)
by
turning
ON
switch
2
(Reader A) and switch
5
(Reader B).
NOTE:
Both door contact and exit button inputs have voltage present on
the circuits. Only connect dry contact devices to these inputs. If the switch #2
or #5 is disabled then there is no forced entry alarm monitoring at the panel.
JP 52
Reader Port B
JP 23
Reader Port A