Continuous Mode 

If you select Continiuous Mode at DIP switch S12 (DIP switch S12=1), the device provides continuous power. It 
also applicable in the Constant Current Mode. Factory setup = Continuous Mode 

 

Over Load Behaviour 

The CPS-EX changes from the standard opartion mode into the high current mode when high and quick over 
load occurs. Thus it provokes a restart after a 30ms break and delivers continous current to the output. This 
special behaviour is a protection for the power supply and for the connected load. 

 

Compensation of Load Line Drop Voltage (Sense ++/--), standard operation mode 

The CPS-EX power supply has a Sense Mode to compensate for the voltage drop over long load lines. The 
compensation amounts to a maximum of 2V per load line. Under certain circumstances, it can be expected to 
apply fairly more complicated external interference suppression. If sense is not used, CON4 Sense +/+ and 
Sense -/- shall necessarily be connected by short bridges to the power outputs (factory setup). 
 
Sense operation: Remove the bridges between Sense +/+, Sense -/- and the power outputs. Connect the sense 
lines directly to the load. It is irrelevant which of the local connections Sense +/+ and Sense -/- are applied. Pay 
attention to the polarity of plus and minus of the load to prevent damage to the power supply. To avoid 
interference, twist the sense lines. In order to reduce inductive effects, we recommend that the load lines 
position is close to each other. In order to supply a pulsating load, the use of an electrolytic capacitor and a 
cermic capacitor has proved. The internal Over Voltage Protection (OVP) of the power supply controls the DC 
power directly to the DC output terminals. In case of an error the OVP acts automatically (see OVP values 
corresponding table).  
 
Operating in the sense mode requires that the maximum output voltage will not be exceeded. Maximum 2V per 
load lead can be compensated. The voltage drop in the load lines decreases the maximum output voltage 
rating. For example for a 30V unit: if the total voltage drop in the load leads is 2V you must substract this value 
from the maximum programmable output voltage 30V – 2V = 28V maximum available voltage at the load. 
 
The sense terminals are directly connected to the power outputs. 
 
                               

Lokal Sensing

                                                                                   

Remote Sensing

 

                               (factory setup)                                                                                    (twisted sense lines) 
 
 
 
 
 

 

Compensation of Load Line Drop Voltage (Sense ++/--) battery charger operation mode 

Remote Sensing as a battery charger 

If the CPS-EX power supply unit is used as a battery charger, it is recommended to refrain from sensing. It can 
lead to severe damage to the power supply, if the polarity of the sense line is confused (field experience: such 
error often occurs when system service is required, e.g. when the batteries are changed). If it is absolutely 
necessary to use sensing, proceed as described in the figure below. Proven approaches are 250mA for the 
fuses and 3...5A load capacity of diodes. 
 
 
 
 
 
 
 
 
 
 

Содержание CPS-EX2000.024

Страница 1: ...value C V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Power Good Relay DC ok Precise dynamics on load change Se...

Страница 2: ...he highest standards of safety and interference suppression The device was developed in accordance with the requirements of IEC CSA UL60950 1 and the EMC standards EN55022 conducted Class B radiated C...

Страница 3: ...ore than 5 seconds in constant current mode to protect a connected defect load The lock can be controlled remotely or repeal by disconnection from the mains again Continuous Mode The unit can be opera...

Страница 4: ...reg 0 5 Ireg 1 Umon 0 5 Imon 1 Uref 1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 20ms 230Vac mains buffering at full load Inrush Curr...

Страница 5: ...Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Curr...

Страница 6: ...76327 Pfinztal Germany S 6 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product may not be used in life s...

Страница 7: ...may not be used in life support systems CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www n...

Страница 8: ...s analog linear to the output voltage The monitor signal for current and voltage is the real value that is measured directly at the output of the power supply If a sense line is connected to compensat...

Страница 9: ...n to the polarity of plus and minus of the load to prevent damage to the power supply To avoid interference twist the sense lines In order to reduce inductive effects we recommend that the load lines...

Страница 10: ...S1 0 0 0 0 0 S2 0 1 1 0 0 S2 0 0 0 0 0 S3 0 0 0 1 0 S3 0 0 0 0 0 S4 0 0 1 1 0 S4 0 0 0 0 0 S5 0 1 1 0 0 S5 0 0 0 0 0 S6 1 0 0 0 1 S6 1 1 1 1 1 S7 0 0 0 1 0 S7 0 0 0 0 0 S8 0 1 1 1 0 S8 0 1 1 1 0 S9 0...

Страница 11: ...the soft start the current and the voltage rises within 100ms continuously to the default set values Between the INH contacts applies a current of typical 2mA Warning against damage in case of incorr...

Страница 12: ...for example defective components external feed voltage it is followed by the shutdown of the power output A periodic restart attempts ticker operation period 1s and a message is triggered The alarm si...

Страница 13: ...down OT The alarm signal OT is high when the temperature of the power supply is higher than the over temperature protection threshold Output Open Collector IMAX 10mA VLOW 0 6V VMAX 30V Fan Fail Signal...

Страница 14: ...e can be operated up to a total voltage of 600Vdc in series Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for se...

Страница 15: ...mbH Gewerbestra e 30 DE 76327 Pfinztal Germany S 15 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product m...

Страница 16: ...2000Vac 500Vdc 1000Vdc Field Test 2s 2000Vac 2000Vac 500Vdc 1000Vdc 60Vdc 1200Vdc 150Vdc 2100Vdc Type and Factorytest are the manufacturer While repeating test damage can occur to the power supply un...

Страница 17: ...ing IP20 Cooling is achieved via front to rear fans In order to ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The har...

Страница 18: ...9 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product may not be used in life support systems 19 48TE Subrack 2U 3U 2U Subrack 48TE for 1 3 CPS EX2...

Страница 19: ...hard mount of the CPS EX2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cool...

Страница 20: ...nting In preparation Safety regulations Please read these instructions completely before using the equipment Keep these instructions on to hand The device may only be operated by trained specialist st...

Отзывы: