Analog Interface CON1 (Connector Model Weidmueller 1277320000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AC OK-1 

Output 

Closers, Signal AC OK 

Relay 

Potential-free 

DC OK-1 

Output

 

Closers, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-2 

Output

 

Center, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-2 

Output

 

Center, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-3 

Output

 

Break, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-3 

Output

 

Break, Signal DC OK

 

Relay

 

Potential-free

 

SB 

Input 

Control Signal Standby

 

Switch / Open Collector 

 

SD 

Input 

Control Signal Shutdown 

Switch / Open Collector 

 

DGND 

Digital Ground 

 

10 

+12V AUX 

Output 

Auxiliary Voltage 

12Vdc/0,5A ±0,5V 30mVpp 

1000uF, O-Ring Diode 

11 

DGND 

Digital Ground 

 

12 

INH 

Input 

Control Signal Inhibit (Interlock) 

Switch 

 

Analog Interface CON2 (Connector Model Weidmueller 1277330000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

DGND 

Digital Ground 

 

TEMP 

Output 

Temperature Control

 

Voltage 10mV/°C 

 

DGND 

Digital Ground

 

 

NC 

NC

 

Not Connected

 

 

No Function 

DCF 

Output

 

Signal DC Failure

 

Open Collector 

 

ACF 

Output

 

Signal AC Failure

 

Open Collector 

 

FF 

Output

 

Signal Fan Failure

 

Open Collector 

 

INH 

Output

 

Signal Inhibit Active 

Open Collector 

 

OT 

Output

 

Signal Over Temperature 

Open Collector 

 

10 

TA 

Output

 

Signal Temperature Alarm 

Open Collector 

Early warning 

11 

OCP 

Output

 

Signal Over Current Protection 

Open Collector

 

 

12 

CC 

Output

 

Signal Constant Current Mode 

Open Collector

 

 

13 

OVP 

Output

 

Signal Over Voltage 

Open Collector

 

 

14 

CV 

Output

 

Signal Constant Voltage Mode 

Open Collector 

 

Analog Interface CON3 (Connector Model Weidmueller 1277340000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AGND 

Analog Ground 

 

Imon 

Output

 

Current Monitor

 

0-5Vdc / 5mA, 0-10Vdc / 5mA 

 

NC 

NC

 

Not Connected

 

 

No Function 

Umon 

Output

 

Voltage Monitor

 

0-5Vdc / 5mA, 0-10Vdc / 5mA 

 

CS 

I/O

 

Current Share Bus (CSB)

 

Parallel Operation 

Bidirectional 

Ireg-OUT 

Output

 

Current Programming Slave

 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

Ureg-OUT 

Output

 

Voltage Programming Slave 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

10*

 

Iadj 

Output

 

Potentiometer Connection Current 

 

With external poti 

11 

Uref 

Output

 

Reference Voltage 

5,2Vdc / 5mA, 10,4Vdc / 5mA 

 

12*

 

Uadj 

Output

 

Potentiometer Connection Voltage 

 

With external poti 

13 

CS 

I/O

 

Current Share Bus (CSB) 

Parallel Operation 

Bidirectional

 

14 

Ireg-IN 

Input

 

Current Programming 

0-5V, 0-10V, 0-20mA, 4-20mA 

 

15 

AGND 

-

 

Analog Ground 

 

16 

Ureg-IN 

Input 

Voltage Programming 

0-5V, 0-10V, 0-20mA, 4-20mA 

 

Analoge Interface CON4 (Connector Model Weidmueller 1277290000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

Sense - 

Input 

Sense Connection 

2V / load line 
 

Sense - 

Input 

Sense Connection

 

-

 

3, 4 

 

 

NC 

Must not be connected

 

5, 6 

 

 

NC 

Sense + 

Input

 

Sense Connection

 

-

 

2V / load line 
 

Sense + 

Input

 

Sense Connection

 

-

 

PIN10/12*

 

when

 

no external control signal shall be used the device can be set with internal potentiometers. Please connect 

Pin10 with Pin14 and Pin12 with Pin16 to operate this mode. 

 
 

Содержание CPS-EX2000.024

Страница 1: ...value C V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Power Good Relay DC ok Precise dynamics on load change Se...

Страница 2: ...he highest standards of safety and interference suppression The device was developed in accordance with the requirements of IEC CSA UL60950 1 and the EMC standards EN55022 conducted Class B radiated C...

Страница 3: ...ore than 5 seconds in constant current mode to protect a connected defect load The lock can be controlled remotely or repeal by disconnection from the mains again Continuous Mode The unit can be opera...

Страница 4: ...reg 0 5 Ireg 1 Umon 0 5 Imon 1 Uref 1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 20ms 230Vac mains buffering at full load Inrush Curr...

Страница 5: ...Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Curr...

Страница 6: ...76327 Pfinztal Germany S 6 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product may not be used in life s...

Страница 7: ...may not be used in life support systems CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www n...

Страница 8: ...s analog linear to the output voltage The monitor signal for current and voltage is the real value that is measured directly at the output of the power supply If a sense line is connected to compensat...

Страница 9: ...n to the polarity of plus and minus of the load to prevent damage to the power supply To avoid interference twist the sense lines In order to reduce inductive effects we recommend that the load lines...

Страница 10: ...S1 0 0 0 0 0 S2 0 1 1 0 0 S2 0 0 0 0 0 S3 0 0 0 1 0 S3 0 0 0 0 0 S4 0 0 1 1 0 S4 0 0 0 0 0 S5 0 1 1 0 0 S5 0 0 0 0 0 S6 1 0 0 0 1 S6 1 1 1 1 1 S7 0 0 0 1 0 S7 0 0 0 0 0 S8 0 1 1 1 0 S8 0 1 1 1 0 S9 0...

Страница 11: ...the soft start the current and the voltage rises within 100ms continuously to the default set values Between the INH contacts applies a current of typical 2mA Warning against damage in case of incorr...

Страница 12: ...for example defective components external feed voltage it is followed by the shutdown of the power output A periodic restart attempts ticker operation period 1s and a message is triggered The alarm si...

Страница 13: ...down OT The alarm signal OT is high when the temperature of the power supply is higher than the over temperature protection threshold Output Open Collector IMAX 10mA VLOW 0 6V VMAX 30V Fan Fail Signal...

Страница 14: ...e can be operated up to a total voltage of 600Vdc in series Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for se...

Страница 15: ...mbH Gewerbestra e 30 DE 76327 Pfinztal Germany S 15 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product m...

Страница 16: ...2000Vac 500Vdc 1000Vdc Field Test 2s 2000Vac 2000Vac 500Vdc 1000Vdc 60Vdc 1200Vdc 150Vdc 2100Vdc Type and Factorytest are the manufacturer While repeating test damage can occur to the power supply un...

Страница 17: ...ing IP20 Cooling is achieved via front to rear fans In order to ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The har...