Temperature Control Signal (TEMP) 

The power supply has a temperature monitor. Here, the temperature of the power supply is continuously 
measured. The signal TEMP provides a voltage U

TEMP

 corresponding to the internal temperature of the power 

supply T

INT

: T

INT

=U

TEMP

/(10mV/°C), U

TEMP

 in mV. Measuring range: +2...+150°C. Output impedance 2kOhm. 

Between the signal TEMP and the power input and the power output is a reinforced Isolation max. 400Vdc. 

 

Temperature Warning (TA) 

The power supply has a Temperature Warning. The signal provides the user the option to save important data 
before the power supply shut down from OT, or to put his system in the emergency mode. The alarm signal TA 
is high when the internal temperature of the power supply is approximately 5°C below the overtemperature 
protection threshold. Output Open Collector I

MAX

=10mA, V

LOW

0,6V, V

MAX

=30V. 

 

Over Temperature Shutdown (OT) 

The alarm signal OT is high when the temperature of the power supply is higher than the over-temperature 
protection threshold. Output Open Collector I

MAX

=10mA, V

LOW

0,6V, V

MAX

=30V. 

 

Fan Fail Signal (FF) 

The power supply fans are continuously monitored. FF occurs when one or both fans have an error (lower 
speed due to bearing contamination, blockage or failures). A failure message is sent: The status signal FF 
applies high. Output Open Collector I

MAX

=10mA, V

LOW

0,6V, V

MAX

=30V. 

 

C/V Chart and Operating Point 

The output voltage set Vout is always linear proportional to the control signal 
Ureg. 
 
The desired control signal is selected via the DIP switcher:  
0-5V, 0-10V, 0-20mA oder 4-20mA.  
 
 
 
 

Model 

Value UA1 (V) 

Value IA1 (A) 

Value UA2 (V) 

Value IA2 (A) 

Pmax (IA1/IA2) 

CPS-EX2000.024 

30Vdc 

66,7A 

24Vdc 

84A 

2001/2016W

 

CPS-EX2000.036 

45Vdc 

44,4A 

36Vdc 

56A 

1998/2016W 

CPS-EX2000.048 

58Vdc 

34,5A 

48Vdc 

42A 

2001/2016W 

CPS-EX2000.072 

90Vdc 

22,2A 

72Vdc 

28A 

1998/2016W 

CPS-EX2000.110 

150Vdc 

13,4A 

110Vdc 

18,2A 

2010/2002W 

 

Inrush Current Limiter (electronic) 

The power supply unit has an electronic current limiter 
(230Vac=14,6A

rms

/20,7A

peak

).  

 
It is a precisely working circuit instead of a usual simple NTC 
solution. The accuracy is ±10%, regardless of the operating 
temperature and the duty cycles (interval 

10s). We recommend 

the smallest circuit breaker a characteristic B with 16A. 

  
 
 
 
 
 

 
 
 

Содержание CPS-EX2000.024

Страница 1: ...value C V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Power Good Relay DC ok Precise dynamics on load change Se...

Страница 2: ...he highest standards of safety and interference suppression The device was developed in accordance with the requirements of IEC CSA UL60950 1 and the EMC standards EN55022 conducted Class B radiated C...

Страница 3: ...ore than 5 seconds in constant current mode to protect a connected defect load The lock can be controlled remotely or repeal by disconnection from the mains again Continuous Mode The unit can be opera...

Страница 4: ...reg 0 5 Ireg 1 Umon 0 5 Imon 1 Uref 1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 20ms 230Vac mains buffering at full load Inrush Curr...

Страница 5: ...Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Curr...

Страница 6: ...76327 Pfinztal Germany S 6 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product may not be used in life s...

Страница 7: ...may not be used in life support systems CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www n...

Страница 8: ...s analog linear to the output voltage The monitor signal for current and voltage is the real value that is measured directly at the output of the power supply If a sense line is connected to compensat...

Страница 9: ...n to the polarity of plus and minus of the load to prevent damage to the power supply To avoid interference twist the sense lines In order to reduce inductive effects we recommend that the load lines...

Страница 10: ...S1 0 0 0 0 0 S2 0 1 1 0 0 S2 0 0 0 0 0 S3 0 0 0 1 0 S3 0 0 0 0 0 S4 0 0 1 1 0 S4 0 0 0 0 0 S5 0 1 1 0 0 S5 0 0 0 0 0 S6 1 0 0 0 1 S6 1 1 1 1 1 S7 0 0 0 1 0 S7 0 0 0 0 0 S8 0 1 1 1 0 S8 0 1 1 1 0 S9 0...

Страница 11: ...the soft start the current and the voltage rises within 100ms continuously to the default set values Between the INH contacts applies a current of typical 2mA Warning against damage in case of incorr...

Страница 12: ...for example defective components external feed voltage it is followed by the shutdown of the power output A periodic restart attempts ticker operation period 1s and a message is triggered The alarm si...

Страница 13: ...down OT The alarm signal OT is high when the temperature of the power supply is higher than the over temperature protection threshold Output Open Collector IMAX 10mA VLOW 0 6V VMAX 30V Fan Fail Signal...

Страница 14: ...e can be operated up to a total voltage of 600Vdc in series Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for se...

Страница 15: ...mbH Gewerbestra e 30 DE 76327 Pfinztal Germany S 15 20 07 2017 01 0 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product m...

Страница 16: ...2000Vac 500Vdc 1000Vdc Field Test 2s 2000Vac 2000Vac 500Vdc 1000Vdc 60Vdc 1200Vdc 150Vdc 2100Vdc Type and Factorytest are the manufacturer While repeating test damage can occur to the power supply un...

Страница 17: ...ing IP20 Cooling is achieved via front to rear fans In order to ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The har...

Страница 18: ...9 721 46596 77 www camtec gmbh com info camtec gmbh com Technical changes and errors reserved This product may not be used in life support systems 19 48TE Subrack 2U 3U 2U Subrack 48TE for 1 3 CPS EX2...

Страница 19: ...hard mount of the CPS EX2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cool...

Страница 20: ...nting In preparation Safety regulations Please read these instructions completely before using the equipment Keep these instructions on to hand The device may only be operated by trained specialist st...

Отзывы: