A sediment trap should be installed at the bottom of the gas line.
The inlet gas pressure to the water heater must not exceed 10.5” w.c. for natural
or 14” w.c. for LP gas. For purposes of input adjustment, the minimum inlet gas
pressure (with main burner on) is shown on the water heater rating plate. If high
or low gas pressures are present, contact your gas supplier for correction
The water heater and its indivdual shutoff valve must be disconnected from the
gas supply piping system during any pressure testing of that system at test
pressures in excess of ½ psi (3.5 kPa). The water heater must be isolated from
the gas supply piping system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test pressures equal to or
less than ½ psi (3.5 kPa).
DO NOT use excessive force (over 31.5 ft lbs.) in tightening the pipe, particularly
if pipe compound is used, as the unit may be damaged.
Compound used on the threaded joints of the gas piping must be of the type
resistant to the action of LP gas. Use compound sparingly and use on male
threads only.
Relief valve
A new pressure relief valve, complying with the Standard for relief Valves and
Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22,
must be installed at the hot water outlet connection of the water heater at the time
of installation. Local codes shall govern the installation of relief valves.
For safe operation of the water heater, be sure that:
● The pressure rating of the relief valve must not exceed 150 psi, the maximum
working pressure of the water heater as marked on the rating plate.
● The BTUH rating of the relief valve must equal or exceed the BTUH input of the
water heater as marked on its rating plate.
● No valve of any type should be installed between the relief valve and the water
heater.
● Discharge from the relief valve should be piped to a suitable drain to eliminate
potential water damage. Piping used should be of a type approved for the
distribution of hot water.
● Hot and cold water lines should be insulated up to the water heater.
● The discharge line must be NO SMALLER than the outlet of the valve and must
pitch downward to allow complete drainage (by gravity) of the relief valve and
discharge line.