Section 9. Program Control Instructions
9-24
WaitLinkTrig (Dest, Reps, Link)
WaitLinkTrig is used to trigger CR9000 scans by a message sent over a
communication link from another CR9000 sent using the OutLink instruction.
WaitLinkTrig is placed immediately after the Scan instruction and pauses the
scan until values are received over the specified link. The Scan interval is
entered as a negative number to tell the CR9000 that it is to use an external
scan trigger input. It should be noted that the CR9000 time stamp is clocked
by the scan. Thus, if the scan rate is set at 2 seconds, but the trigger is
activated every 4 seconds, the time stamp will still increment only 2 seconds
every time the trigger activates the scan (increment value will be off by a factor
of 2).
Parameter
& Data Type
Enter
Dest
Variable or
array
Variable or array in which to store the value(s) received over the link. This instruction does
not require that any values be stored. If Reps are set to 0, no values will be loaded into the
destination variable.
Reps
Constan
The number of values to expect over the link and store in the destination variable. Enter 0 and the scan
still waits for the link but does not store any values.
Link
A code specifying the link to receive the data.
Constant
Value Link
1
T-Link,
(Link 1
)
2
Fiber Optic Link,
(Link 2)
Содержание CR9000
Страница 6: ...CR9000 Table of Contents iv This is a blank page ...
Страница 22: ...CR9000 Overview OV 16 This is a blank page ...
Страница 26: ...Section 1 Installation 1 4 CR9000 FIGURE 1 1 3 CR9000 Battery Pack ...
Страница 72: ...Section 3 CR9000 Measurement Details 3 28 This is a blank page ...
Страница 88: ...Section 5 Program Declarations 5 6 This is a blank page ...
Страница 217: ...This is a blank page ...