Section 7. Measurement Instructions
7-17
Parameter
& Data Type
Enter
CANBUS INSTRUCTION PARAMETERS
6
Normal; self-test. The SDM-CAN will perform a successful
transmission even if there is no acknowledgment from an
external CAN node. Frames received correctly from an external
node are acknowledged.
7,8 Not
Used.
9
Leave switch setting unchanged.
33
Read SDM-CAN's internal switches. Place results in the array specified in the
Dest
ination parameter.
StartBit
Constant
StartBit is used to identify the least significant bit of the data value within the CAN data frame
to which the instruction relates. The bit number can range from 1 to 64 (there are 64 bits in a
CAN data frame). The SDM-CAN adheres to the ISO standard where the least significant bit
is referenced to the right most bit of the data frame. If a negative value is entered, the least
significant bit is referenced to the left most bit of the data frame.
NumBits
Constant
NumBits specifies the number of bits that will be used in a transaction. The number can range
from 1 to 64 (there are 64 bits in a CAN data frame).
The SDM-CAN can be configured to notify the datalogger when new data is available by
setting a control port high. This allows data to be stored in the datalogger tables faster than the
program execution interval. This interrupt function is enabled by entering a negative value for
this parameter.
Note: This parameter may be overridden by a fixed number of bits, depending upon the
data type selected.
NumVals
The number of values (beginning with the value stored in the Dest array) that will be
transferred to or from the datalogger during one operation. For each value transferred, the
Number of Bits (NumBits) will be added to the Start Bit number so that multiple values can be
read from or stored to one data frame.
Mult, Offset
Constant,
Variable,
Array, or
Expression
A multiplier and offset by which to scale the raw results of the measurement. See the measurement
description for the units of the raw result; a multiplier of one and an offset of 0 are necessary to output in
the raw units. For example, the
TCDiff
instruction measures a thermocouple and outputs temperature in
degrees C. A multiplier of 1.8 and an offset of 32 will convert the temperature to degrees F.
CSAT3 (Dest, Reps, Address, Command)
Communicates with the CSAT3 three dimensional sonic anemometer. See
CSAT3 manual for more information.
INT8 INTERVAL TIMER
Used to control the INT8, an 8 Channel Interval Timer module, using the
CR9000.
Syntax
INT8
(Dest, Address,Config8_5,Config4_1,
Funct8_5,Funct4_1,OutputOpt,CaptureTrig, Mult, Offset
)
Содержание CR9000
Страница 6: ...CR9000 Table of Contents iv This is a blank page ...
Страница 22: ...CR9000 Overview OV 16 This is a blank page ...
Страница 26: ...Section 1 Installation 1 4 CR9000 FIGURE 1 1 3 CR9000 Battery Pack ...
Страница 72: ...Section 3 CR9000 Measurement Details 3 28 This is a blank page ...
Страница 88: ...Section 5 Program Declarations 5 6 This is a blank page ...
Страница 217: ...This is a blank page ...