SECTION 1. FUNCTIONAL MODES
1-13
TABLE 1.8-5 Transferring a Program using a
Storage Module
Key entry
Display
∗
D
13:00
7NA
7N:00
(N is Storage Module
address 1-8)
You may now enter one of the following options:
1x
Save Program x to Storage
Module (x = 1-8)
2x
Load Program x from Storage
Module (x = 1-8)
3x
Erase Program x in Storage
Module (x = 1-8)
The datalogger can be programmed on power-
up using a Storage Module. If a program is
stored as program number 8, and the Storage
Module is connected to the datalogger I/O at
power-up, program number 8 is automatically
loaded into the active program area of the
datalogger and run.
1.8.3 FULL/HALF DUPLEX
The *D Mode can also be used to set
communications to full or half duplex. The default
is full duplex, which works best in most situations.
TABLE 1.8-6. Setting Duplex
Key entry
Display
∗
D
13:00
9A
09:0x
If x=0 the CR510 is set for full duplex.
If x=1 the CR510 is set for half duplex.
You may now change the option:
0A
Set full duplex
1A
Set half duplex
1.8.4 SET DATALOGGER ID
Command 8 is used to set the datalogger ID.
The ID can be moved to an input location with
Instruction 117 and can then be sampled as
part of the data.
TABLE 1.8-7 Setting Datalogger ID
Key Entry
Display
∗
D
13:00
8A
08:0XXX
Where XXX are 0s or the current ID. You may
now key in the ID (1-254, excluding 13).
1.8.5 SETTING POWERUP OPTIONS
Setting options for the Program on Powerup
allows the user to specify what information to
retain from when the datalogger was last on.
This allows Flag/Port status, the User Timer,
and the Input/Intermediate Storage to be
cleared or not cleared.
Table 1.8-8. Setting Powerup Options
Key entry
Display
∗
D
13:00
10A
10:0X
Where X is the powerup option currently
selected. You may now change the option:
0A
Clears input locations, ports, flags, user
timer, and intermediate storage locations.
1A
Clears intermediate storage only (leaves
Input Storage, Flags/Ports, and User Timer
as is).
2A
Doesn’t clear anything.
3A
Do not change power-up settings.
Содержание CR510
Страница 1: ...CR510 DATALOGGER OPERATOR S MANUAL REVISION 2 03 COPYRIGHT c 1986 2003 CAMPBELL SCIENTIFIC INC ...
Страница 2: ...This is a blank page ...
Страница 4: ...This is a blank page ...
Страница 10: ...This is a blank page ...
Страница 44: ...SECTION 1 FUNCTIONAL MODES 1 14 This is a blank page ...
Страница 56: ...SECTION 3 INSTRUCTION SET BASICS 3 8 ...
Страница 104: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 8 This is a blank page ...
Страница 128: ...SECTION 10 PROCESSING INSTRUCTIONS 10 8 This is a blank page ...
Страница 144: ...SECTION 12 PROGRAM CONTROL INSTRUCTIONS 12 10 This is a blank page ...
Страница 172: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 10 This is a blank page ...
Страница 176: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Страница 184: ...This is a blank page ...
Страница 188: ...APPENDIX D DATALOGGER INITIATED COMMUNICATIONS D 4 This is a blank page ...
Страница 196: ...APPENDIX F MODBUS ON THE CR10 X AND CR510 F 4 This is a blank page ...
Страница 197: ...APPENDIX G TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Страница 198: ...This is a blank page ...
Страница 200: ...This is a blank page ...
Страница 206: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Страница 222: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Страница 238: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Страница 240: ...This is a blank page ...