Section 12. Program Control Instructions
12-4
Notes:
Edlog allocates only one of the input locations used in parameters 5 and 7 of
this instruction. The additional input locations must be inserted manually using
the Input Location Editor.
If this instruction is used to retrieve a value or set a value in the remote
datalogger's public (or input location) table (i.e., code 26 or 27 is used in
parameter 3), Instruction 63 or 68 must follow this instruction to enter the
variable name that will be accessed.
Index parameter 3 to delay execution of subsequent program instructions until
the datalogger receives a valid response or error from the remote. Otherwise,
the PakBus command is queued, the datalogger proceeds to the next
instruction, and the communications are handled later when the remote replies.
Port
The communications port that will be used by the local PakBus datalogger
during the execution of this instruction. Valid options are:
Code
Description
0
Modem Enabled Device, 300
1
Modem Enabled Device, 1200
2
Modem Enabled Device, 9600
3
Modem Enabled Device, 76800
4
Modem Enabled Device, 2400
5
Modem Enabled Device, 4800
6
Modem Enabled Device, 19200
7
Modem Enabled Device, 38400
16
SDC 6 (COM 310)
17
SDC 7
18
SDC 8
Note: The CR10X-TD and CR510-TD have limited communication rates and
do not support options 4 through 7.
Address
When a PakBus command is being issued, this address refers to the PakBus
address of the datalogger. When a Modbus command is being issued, this
address refers to the Modbus address. The PakBus and Modbus addresses in
the datalogger cannot be set to the same number.
If this instruction is used within a loop, index this parameter to automatically
increment the address with each pass through the loop. When this parameter is
indexed, program execution will be delayed until a response is received from
the remote datalogger.
Содержание CR510
Страница 1: ...CR510 DATALOGGER OPERATOR S MANUAL REVISION 2 03 COPYRIGHT c 1986 2003 CAMPBELL SCIENTIFIC INC ...
Страница 2: ...This is a blank page ...
Страница 4: ...This is a blank page ...
Страница 10: ...This is a blank page ...
Страница 44: ...SECTION 1 FUNCTIONAL MODES 1 14 This is a blank page ...
Страница 56: ...SECTION 3 INSTRUCTION SET BASICS 3 8 ...
Страница 104: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 8 This is a blank page ...
Страница 128: ...SECTION 10 PROCESSING INSTRUCTIONS 10 8 This is a blank page ...
Страница 144: ...SECTION 12 PROGRAM CONTROL INSTRUCTIONS 12 10 This is a blank page ...
Страница 172: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 10 This is a blank page ...
Страница 176: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Страница 184: ...This is a blank page ...
Страница 188: ...APPENDIX D DATALOGGER INITIATED COMMUNICATIONS D 4 This is a blank page ...
Страница 196: ...APPENDIX F MODBUS ON THE CR10 X AND CR510 F 4 This is a blank page ...
Страница 197: ...APPENDIX G TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Страница 198: ...This is a blank page ...
Страница 200: ...This is a blank page ...
Страница 206: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Страница 222: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Страница 238: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Страница 240: ...This is a blank page ...