TIMES 13
*
AUTOTEST TIME
[0..255] HOURS 000
▲
▼
▼
▲
+ -
▼
▲
BATTER.TEST TIME
[0..255] MIN 060
+ -
GENERAL ALRM.
[0..255] MIN 090
+ -
DELAY: POWER OFF
[0..255] MIN 060
+ -
▼
▲
SABOTAGE
[0..255] SEC 090
+ -
TECH. ALARM
[0..255] SEC 090
+ -
BURGLR. ALRM
[0..255] SEC 000
+ -
BUZZER OUTPUT
[0..255] SEC 000
+ -
EXIT TIME
[0..255] MIN 050
+ -
ENTRANC1 TIME
[0..255] MIN 030
+ -
ENTRANC2 TIME
[0..255] MIN 040
+ -
Autotest time: (Default:
000
)
S
A
This sets after how many hours the control unit must regularly and automatically carry out an
autotest of operation The first autotest after starting up the control unit is carried out after a
period defined as AUTOTEST INTERVAL
If the value is set at 000, the autotest is not carried out
Example: this function is generally used by security as system survival
Telephone 15: security firm number; format
CONTACT-ID
; system code
XXXX
Autotest time
24
hours
In telephone notifications: telephones for autotest notification
--------------#-
Battery test time: (Default:
060
)
S
A
This determines how often (in minutes) the control unit should automatically carry out a DY-
NAMIC BATTERY TEST If the value is set at 0 the test is disabled In the event of a failed battery,
the failure LED flashes and continues to flash until the next test; it is also possible to associate
an output or a remote communication
N B the failure status remains active until the next “BATTERY TEST” To remove the failure sta-
tus after replacing the battery, carry out a manual "BATTERY TEST" by accessing the technical
menu
Power down notification delay: (Default:
060
)
S
A
This determines after what period the LACK of GRID voltage is considered an anomaly The
POWER DOWN event is entered into the events memory In the event of a power outage, the
failure LED stays permanently on
m
Setting a time greater than 60 minutes invalidates the reference standard
General alarm time: (Default:
090
)
F
S
A
During the GENERAL ALARM TIME, the GENERAL ALARM RELAY is active
The general alarm condition is determined by the activations of the inputs
Sabotage time: (Default:
090
)
F
S
A
Alarm time associated to 24-hour inputs or to tamper/tempering alarms
Technical alarm time: (Default:
090
)
F
S
A
Alarm time associated to technical type inputs
Burglary alarm time: (Default:
000
)
F
S
A
Alarm time associated to burglary type inputs
Buzzer output time: (Default:
000
)
F
S
A
The BUZZER ALARM condition is determined by activations of the inputs which have their
"Buzzer Output" property set to ON
Exit time: (Default:
050
)
F
S
A
During the EXIT TIME the control unit checks the conditions of the inputs and notifies the pres-
ence of open inputs This notification occurs: visually on the keypads and on the reader LEDs
and acoustically on the keypad buzzer
Entry time 1 and 2: (Default 1:
030
) (Default 2:
040
)
F
S
A
When the system is armed, unbalancing of a DELAYED 1 or 2 type input activates the respective
ENTRY TIME counter During the ENTRY TIME, the control unit does not trigger an alarm if PATH
or DELAYED-type inputs are unbalanced
At the end of the ENTRY TIME, if the system is not DISARMED, a GENERAL ALARM is triggered
m
Setting a time greater than 45 seconds invalidates the reference standard