User Manual – Rev B
FCS Series II
3. Unpacking and Installation
3.1 Unpacking
Inspect the unit for any possible shipping damage immediately upon receipt. If damage is
evident, notify the carrier.
DO NOT
return an instrument to the factory without prior approval.
Do not destroy the packing container until the unit has been inspected for damage in shipment.
If possible, retain the container in the event the system ever has to be returned to the factory for
either repair of upgrades.
A forklift should be used to remove the FCS cabinet from its shipping crate. Once on a level
floor, the cabinet can be pushed in place using it’s own casters. Levelers at each corner may be
used to prevent the unit from moving. Levelers are not intended to support the entire weight of
the cabinet howewer.
.
WARNING: This power source weighs approximately 900 lbs / 400 Kg per chassis
Obtain adequate help when moving or installing the unit. Make sure the floor on
es unit is installed can support the weight of the unit.
which the FSC II Seri
3.2 Power Requirements
The FCS Series II power Source has been designed to operate from a three-phase, three wire
0 V
LL
with optionally configured input settings. All three phase input is three wire plus
round.
(Wye or Delta) AC input line. A protective earth connection is required as well. (PE).
Available three-phase input setting is 208 V
LL
nominal for standard FCS18 models or 230, 380,
415 or 48
g
CAUTION: Do not connect 400Vor 480V into a unit designed for 208V use. The result
could be a severely damaged unit. Always check the input rating on the model
number tag before connecting AC input power. AC voltage input settings CANNO
be changed in the field. Contact Ca
T
lifornia Instrument customer service to obtain
figuration.
support for input recon
3.3 Mechanical Installation
The FCS II Series AC power sources can be used free standing on a solid surface. The units
are fan cooled, drawing air in from the front and exhausting at the rear. The back of each unit
must be kept clear of obstruction and a 6” clearance must be maintained to the rear. Spec
consideration of overall airflow characteristics and the resultant internal heat r
ial
ise must be
e EUT must be of
equal
en
unit(s). To turn the system off, turn OFF the Auxiliary unit(s) first and then the
Master unit.
considered at all times to avoid self heating and over temperature problems.
Multi chassis configurations such as the FCS36/2 or FSC54/3 consist of two or three self-
contained FCS18 power sources. They must be connected through the system interface using
the supplied DB25 to DB25 cable. Output wiring from each chassis to th
wire gage and length
to ensure proper current sharing between units.
Note that for multi-chassis systems, it is recommended to turn the Master unit ON first and th
the Auxiliary
California Instruments
26
Содержание FCS Series II
Страница 4: ...User Manual Rev B FCS Series II California Instruments 4...
Страница 27: ...User Manual Rev B FCS Series II California Instruments 27...
Страница 28: ...User Manual Rev B FCS Series II Figure 3 1 Rear Panel Connector Locations California Instruments 28...
Страница 35: ...User Manual Rev B FCS Series II Figure 3 4 FCS54 3 3 Wiring Diagram Three Phase mode California Instruments 35...
Страница 36: ...User Manual Rev B FCS Series II Figure 3 5 FCS54 3 1 Wiring Diagram Single Phase mode California Instruments 36...
Страница 89: ...FCS Series II 89 Figure 5 1 FCS System Block Diagram User Manual Rev B California Instruments...
Страница 92: ...User Manual Rev B FCS Series II Figure 5 2 Power Amplifier Exploded View California Instruments 92...
Страница 95: ...User Manual Rev B FCS Series II Figure 6 1 Calibration Setup California Instruments 95...
Страница 109: ...User Manual Rev B FCS Series II Figure 7 1 Front panel location Figure 7 2 Fuse Locations California Instruments 109...
Страница 118: ...User Manual Rev B FCS Series II ure 8 4 Voltage Modulation Frequency characteristics Fig California Instruments 118...