iL Series User Manual
California Instruments
Rev B
3
The following descriptions apply to all models in the California Instruments iL Series
product line. Specifically, the following models are included:
Table 2: iL Series model numbers
Model
Maximum
power output
Operating Modes
3000iL
3000 VA
Single or Three phase. 208 V L-L 3ø input
3000iL-400
3000 VA
Single or Three phase. 400 V L-L 3ø input
4500iL
4500 VA
Single or Three phase. 208 V L-L 3ø input
4500iL-400
4500 VA
Single or Three phase. 400 V L-L 3ø input
4801iL
4800 VA
Single phase output. 208 V L-L 3ø input
4801iL-400
4800 VA
Single phase output. 400 V L-L 3ø input
1.4.1 Capabilities
•
Programmable AC voltage, frequency, phase, and current limit.
•
Sine, square, clipped sine, and user-definable waveforms.
•
Voltage and frequency slew control.
•
Synthesized waveform generation for high resolution and accuracy in frequency,
low waveform distortion, and glitch-free phase transitions.
•
Step and pulse output transients for generating surge, sag, dropout, and other
line disturbance simulations.
•
Nonvolatile list programming for generating complex output transients or test
sequences.
•
Extensive measurement capability:
•
Ac rms, dc, ac+dc voltage and current and peak current.
•
Real, reactive, and apparent power.
•
Harmonic analysis of voltage and current waveforms gives amplitude,
phase, and total harmonic distortion results up to the 50th harmonic.
•
Triggered acquisition of digitized voltage and current with extensive post-
acquisition calculations.
•
Additional total power and neutral current measurements in the three-phase
mode.
•
All measurements made with 16-bit resolution.
•
Trigger In and Trigger Out for synchronizing transient events or measurements
with external signals.
•
Front panel control with 14-character vacuum fluorescent display, keypad, and
rotary pulse generators for voltage and frequency settings.
•
Built-in IEEE-488 and RS-232C interface programming with SCPI command
language.
•
Non-volatile state and waveform storage and recall.
•
Over-voltage, over-current, over-temperature, and RI/DFI protection features.
•
Built-in output disconnect relays.
•
Extensive selftest, status reporting, and software calibration.
1.4.2 Front Panel Controls
The front panel has both rotary (rotary pulse generator - RPG) and keypad controls
for setting the output voltage and frequency. The panel display provides digital
readouts of a number of output measurements. Annunciators display the operating
status of the AC source. System keys let you perform system functions such as
setting the IEEE-488 address and recalling operating states. Front panel Function
Содержание 3000iL
Страница 9: ...iL Series User Manual California Instruments Rev B ix page intentionally left blank...
Страница 10: ......
Страница 37: ...iL Series User Manual California Instruments Rev B 27...
Страница 84: ...iL Series User Manual 74 Rev B California Instruments Figure 21 Troubleshooting Diagram for No Output Present...
Страница 89: ...iL Series User Manual California Instruments Rev B 79 Figure 23 AC Power Source Block Diagram...
Страница 93: ...iL Series User Manual California Instruments Rev B 83 Figure 25 AC Input Board Parts Location...
Страница 94: ...iL Series User Manual 84 Rev B California Instruments Figure 26 Mother Board Parts Location...