23
Inspection and commissioning
ALL OPERATIONS DESCRIBED IN THIS PARAGRAPH ARE EXCLUSIVE COMPETENCE OF AUTHORISED
BYOU STAFF, IN COMPLIANCE WITH THAT ENVISIONED IN THIS MANUAL AND THE STANDARDS IN
FORCE.
The respect for the indications given below is indispensable to
guarantee the maximum safety of the automation.
The BYOU authorised technician must perform all tests
envisioned by the Law, Standards and Regulations in force
depending on the risks present, particularly respecting all
requisites of the EN 12445 Standard, which establishes the
test methods for gate automations.
INSPECTION
1 Check that the model selected is suitable for the type of appli-
cation and that all automation components have been installed
correctly, with respect to the indications in this manual.
2 Test opening and closure and control that the movement of
the leaf is regular without friction points.
3 Check that all electric connections are made correctly and
with cables that are in compliance with the Standards.
4 Check the correct functioning of photocells, transmitters, key
selectors, manual release devices.
5 For the photocells, check that on the passage of a cylinder
with diameter of 5 cm and length of 30 cm the switch-over takes
place on the optical axis with the consequent movement stop.
The photocells must intervene when passing the cylinder in
proximity of the TX, in proximity of the RX and in the centre.
6 Take the measurement of the force of impact according to that
indicated by the EN 12445 Standard, intervening, if necessary
on the “Regulation of the motor thrust (PMOT) paragraph.
7 Replace the temporary power supply cable with a mains con-
nection that is in compliance with the Standards in force and
the type of installation.
COMMISSIONING
Commissioning of the automation can only be performed
if all of the previously-described inspection phases have
had a positive result.
1 Apply the warning plate, supplied with the automation, to the
gate in a well-visible position.
2 Apply a plate to the gate that contains the following data:
Type of automation, name and address of the person in charge
of commissioning (manufacturer), serial number, year of manu-
facture and CE mark.
3 Realise the technical file as per indications of the EN 12445
Standard, attaching the entire drawing (e.g. figure 2, electric
wiring diagrams (e.g. figure 5), risk analysis and solutions
adopted, declaration of conformity of the manufacturer of the
devices used (included in this manual).
4 Fill in and supply the owner of the automation with the dec-
laration of conformity.
5 Realise and supply the owner with the “user guide” for the
automation, also using the user guide present in this manual.
6 Realise and supply the owner of the automation with the
periodical maintenance plan.
7 Do not start the automation before having informed the
owner completely regarding the dangers and risks deriving
from incorrect use of the automation.
Safety devices
IMPORTANT!READ CAREFULLY!
In order to comply with regulations
EN 12445
the installation
of resistive edges is compulsory.
It will be duty of the technician responsible for the installation
making a risk analysis and decide where and when install the
resistive edge.
BYOU can provide all the devices necessary for your instal-
lation and relative accessories , contact your trusted supplier
for any further information.
On the picture below an example of application on the primary
closing edges.