Parameter Description | 8
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
31 / 56
8.3 Analogue Inputs
P3.1 and P3.5 AI1 and AI2 Signal Range
Range of the electrical signal.
0: 0-100 %: 0 ... 10 V or 0 ... 20 mA
1: 20-100 %: 2 ... 10 V or 4 ... 20 mA
P3.2 and P3.6 AI1 and AI2 Custom Min.
Customized value for minimum signal. Effective when different than 0%.
P3.3 and P3.7 AI1 and AI2 Custom Max
Customized value for maximum signal. Effective when different than 100%.
P3.4 and P3.8 AI1 and AI2 Filter Time
Low pass filter time constant, to reduce noise. When this parameter is given a value
greater than 0 the function that filters out disturbances from the incoming analogue
signal is activated.
Long filtering time makes the regulation response slower!
%
P3.2
t
unfiltered signal
filtered signal
63 %