8 | Parameter Description
36 / 56
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
- Main Run command is reset
- Quick stop digital input is restored (or fieldbus command is cleared).
- Alarm 63 is shown when quick stop is active.
P4.18 Stop Mode Activation
0: Normal stop (is defined in P1.14)
1: Quick stop (A specific digital input (see P4.17) or command from fieldbus is defined
to activate quick stop. Stop mode is always by ramping and the deceleration time is
defined in P2.25.)
2: Accurate stop (This function gives to Start signals 1 and 2 (defined in P4.1 and
P4.2) the maximum repeatability in achieving the stop of the drive.)
NOTE: P4.1 and P4.2 must be within the values 1-6. P1.14 must be set as ramp stop.
There is no ramp time change. This selection disables the quick stop signal.
8.5 Digital Outputs
P5.1 to P5.3 Relay Output RO1, RO2 and Digital Output DO1
Function for relays and digital output.
Selection Selection name
Description
0
Not used
1
Ready
Frequency inverter is ready to operate
2
Run
Frequency inverter operates (motor is running)
3
General fault
A fault trip has occurred
4
General fault inverted
A fault trip has NOT occurred
5
General alarm
6
Reversed
The reverse command has been selected
7
At speed
The output frequency has reached the set ref-
erence
8
Frequency supervision
Output frequency is over /under the limit set
with parameters P7.1 and P7.2
9
Current supervision
Motor current is over the limit set with para-
meter P7.3
10
Analogue inputs supervi-
sion
Analogue inputs selected with parameter P7.4
is over/under the limits set in P7.5 and P7.6
11
Fieldbus bit1
Bit from fieldbus aux control word
12
Fieldbus bit2
Bit from fieldbus aux control word
13
External brake
The drive is running and the threshold for brake
open have been reached
P5.4 and P5.5 Relay Output 1 ON Delay and OFF Delay
Adjustable delays for ON/OFF transitions.