8.8 Autoreset
P10.1 Automatic Fault Reset
0: Disabled
1: Enabled
The automatic reset function deletes fault state when the fault cause has been elimin-
ated and the wait time P10.2 has elapsed. Parameter P10.4 determines the maximum
number of automatic resets that can be effected during the trial time set by parameter
P10.3. The time count starts from the first automatic reset. If the number of faults de-
tected during the trial time exceeds the values of trials, the fault status becomes per-
manent and a reset command is needed.
P10.2 Wait Time
Time after which the converter attempts to restart the motor automatically after the
fault has been eliminated.
P10.3 Trial Time
Total time for reset attempts.
P10.4 Automatic Reset Tries
Trials attempted during time P10.3.
P10.5 Start Function
Start function after an automatic fault reset.
0: Start with ramp
1: Flying start
2: As defined in P1.13
8.9 Fieldbus
P11.1 to P11.8 ProcessDataOut 1-8 Selection
Parameter couples read only variables to output process data 1 to 8.
0: Output frequency
1: Motor speed
2: Motor current
3: Motor voltage
4: Motor torque
5: Motor power
6: DC link voltage
7: Active fault code
8: Analogue AI1
9: Analogue AI2
10: Digital inputs state
11: PID actual value
12: PID set point
P11.9 FB Aux CW Selection
Parameter defines the input process data coupled to Aux Control Word.
0: not used