Commissioning "Keypad" | 4
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
9 / 56
4.3 Menu Structure
The parameters on the keypad are arranged in menus. An arrow on the left of the dis-
play shows the active menu.
Initial press BACK/RESET key to activate the menu selection (arrow is blinking).
Use the UP and DOWN arrows key to move between the menus.
Press OK key to enter the submenu of a group.
Press BACK/RESET key to return back to former level.
Code
Designation
Description
REF
Reference
Reference value
MON
Monitor
Monitoring values
PAR
Parameter
Application parameters
FLT
Fault
System menu
Active fault
History fault
4.4 Changing Values
• Select the parameter to be changed.
• Press the OK key to edit the value.
• Set the new value by using the arrow keys. You can also move from digit to digit
with the arrow keys LEFT/RIGHT if the value is numerical.
• Confirm changes with OK key or ignore change by returning to previous level with
BACK/RESET key.
4.5 Remote and Local Control Place
The LOC/REM key is intended for switching between remote control place and local
control place.
The control place is the source of control where the frequency inverter can be started
and stopped. Every control place has its own parameter for selecting the frequency
reference source.
The remote-control place is determined by parameter and is indicated by an arrow on
I/O or BUS on the display of the keypad.
The local control place is always the keypad and is indicated by an arrow on KEYPAD
on the display of the keypad.
CAUTION!
Before removing the keypad from the vacuum pump, the control place must be reset
to remote control to avoid a fault message of the vacuum pump (error code 52 keypad
communication fault).
The fault massage is only resettable by using the keypad again to change the control
place!