Output Power:
Connect output lead wires, coming from the down tube, Orange (labeled
1
), Yellow (labeled
2
) and Green/Yellow as follows:
•
Green/Yellow to
green
terminal block ( for double ceiling version connect second Green/
Yellow to any available
green
terminal blocks)
•
Orange to terminal block labeled
1
(and
3
for double ceiling version) (+)
•
Yellow to terminal block labeled
2
(and
4
for double ceiling version) (
-
)
Input Power (from wall switch furnished by End User):
•
Connect one (
BRN
) wire to terminal block labeled "
L
" line.
•
Connect one (
BLU
) wire to terminal block labeled
“
N
" neutral.
•
Connect (
YEL/GRN
) ground wire to either of green terminal blocks.
NOTE:
Mains wire color designation can vary and be subject to National or Local Electrical
codes.
Figure 36C: Single or double ceiling wiring diagram (single ceiling shown)
6.9.2 Ceiling Mount Wiring
Ground (G)
Neutral (N)
Line (L)
Field replaceable
fuse T2A 250V
All I/O wiring to the ceiling
mount must be routed
through provided opening