7
SECTION VII - BURNER SPECIFICATIONS
BOILER
MODEL
BURNER
MIN.
INPUT
(GPH)
BURNER
MAX.
INPUT
(GPH)
BURNER
MODEL
AIR
TUBE
COMB.
BURNER SETTINGS
PUMP
PRESSURE
(PSI)
NOZZLE
MAKE
NOZZLE
DATA
HEAD
LOW FIRE
AIR OR
SHUTTER
HIGH FIRE
AIR OR
BAND
LOW
FIRE
HIGH
FIRE
GPH X
ANGLE
- TYPE
MPC4
1.75
3.55
CF500
CF60KK
3
10
2
N/A
150
Delavan
2.75 X 70 - B
MPC5
3.0
5.5
CF800
CF60KH
3
8.5
0
N/A
150
Delavan
4.50 X 70 - B
MPC6
4.0
7.1
CF1400
CF66KD
4
43
48
150
250
Delavan
4.50 X 60 - B
MPC7
4.0
8.7
CF1400
CF66KE
6
45
51
150
300
Delavan
5.00 X 45 - B
MPC8
7.0
10.2
CF2300
CF66KG
1
37
47
150
300
Delavan
6.00 X 45 - B
MPC9
7.0
11.8
CF2300
CF66KG
7
39
41
150
295
Hago
7.00 X 45 - P
MPC10
7.0
13.4
CF2300
CF66KG
9
43
54
140
280
Delavan
8.00 X 45 - B
MPC11
10.0
15.0
CF2500
CF66KP
2
22
35
275
275
Hago
4.50 X 45 - P
MPC12
10.0
16.6
CF2500
CF66KP
2
23
41
300
300
Hago
5.00 X 45 - P
MPC13
10.0
18.2
CF2500
CF66KP
5
24
38
300
300
Hago
5.50 X 45 - P
MPC14
10.0
19.8
CF2500
CF66KP
6
26
43
275
275
Hago
6.00 X 45 - P
MPC15
10.0
21.5
CF2500
CF66KP
9
25
40
270
270
Hago
6.50 X 45 - P
MPC16
17.0
23.0
CF3500
CF114KR
7
29
42
275
275
Hago
7.00 X 45 - P
MPC17
17.0
24.5
CF3500
CF114KR
8
30
51
275
295
Hago
7.50 X 45 - P
MPC18
17.0
26.0
CF3500
CF114KR
8
29
68
265
265
Hago
8.00 X 45 - P
Table XIIIa: Beckett #2 Oil Burner Specifications
BOILER
MODEL
BURNER
MIN.
INPUT
(MBH)
BURNER
MAX.
INPUT
(MBH)
BURNER
MODEL
DAMPER SETTINGS
MANIFOLD PRESSURE
(“WC)
MINIMUM
INLET
PRESSURE
(“WC)
LOW
FIRE
HIGH
FIRE
SHUTTER
BAND
LOW FIRE
(START)
HIGH
FIRE
MPC4
300
500
CG10.3
N/A
N/A
6
0
1.0
1.8
2.80
MPC5
300
773
CG10.5
N/A
N/A
10
0
1.6
3.2
4.80
MPC6
350
995
CG15.2
26
45
N/A
N/A
1.15
3.15
4.30
MPC7
350
1216
CG15.3
29
66
N/A
N/A
1.1
3.5
4.60
MPC8
550
1438
CG25.1
16
45
N/A
N/A
1.1
3.6
4.70
MPC9
550
1660
CG25.2
22
53
N/A
N/A
0.8
3.57
4.37
MPC10
550
1881
CG25.3
25
54
N/A
N/A
0.75
3.4
4.15
MPC11
550
2103
CG25.4
27
52
N/A
N/A
0.9
3.6
4.50
MPC12
730
2325
CG50.1
28
72
N/A
N/A
0.9
4.2
5.10
MPC13
730
2547
CG50.2
20
39
N/A
N/A
0.8
3.6
4.40
MPC14
730
2769
CG50.3
22
39
N/A
N/A
0.7
3.4
4.10
MPC15
730
2991
CG50.3
22
44
N/A
N/A
0.65
4.0
4.65
MPC16
730
3213
CG50.3
21
46
N/A
N/A
0.6
4.3
4.90
MPC17
730
3435
CG50.4
24
47
N/A
N/A
0.7
4.0
4.70
MPC18
730
3657
CG50.4
25
72
N/A
N/A
0.7
4.9
5.60
Table XIIIb: Beckett Gas Burner Specifications
NOTICE
MPC boiler ratings and capacities are based upon the following burners, pump pressures, nozzle sizes and
manifold pressures. Refer to instructions furnished with burner for additional information regarding proper
installation, fuel piping, wiring details, burner adjustments, service instructions and burner start-up.
Содержание MPC
Страница 19: ...19 Figure 5 Manual or Hydraulic Draw up Section Assembly ...
Страница 28: ...28 Table VII Modular Return Water Mixing Tube RWMT RC ...
Страница 29: ...29 Figure 13 Return Water Mixing Tube RC Assembly and Installation ...
Страница 78: ...78 Figure 56 MPC Common Bare Boiler Components ...
Страница 80: ...80 Figure 56 MPC Common Bare Boiler Components continued ...
Страница 82: ...82 Figure 57 MPC Front Center Section Frame Rail Assembly ...
Страница 84: ...84 Figure 58 MPC Rear Section Frame Rail Assembly ...
Страница 86: ...86 Figure 59 MPC Return Water Mixing Tube RC Assembly ...
Страница 88: ...88 Figure 60 MPC Heat Exchanger Insulation Wrapper ...
Страница 90: ...90 Figure 61 MPC Internal Wiring Harness Components ...
Страница 92: ...92 Figure 62 MPC Jacket Panel Assembly ...
Страница 94: ...94 Figure 62 MPC Jacket Panel Assembly continued ...
Страница 96: ...96 Figure 63 MPC 2 nd and 3 rd Pass Flueway Baffles ...
Страница 98: ...98 Figure 64 MPC Standard 50 PSI Trim Control with 30 PSI and 80 PSI Working Pressure Trim Options ...
Страница 100: ...100 Figure 64 MPC Standard 50 PSI Trim and Control with 30 PSI and 80 PSI Working Pressure Trim Options continued ...
Страница 102: ...102 Figure 65 MPC Optional Controls ...