51
1. In most cases the burner adapter plate carton for the
specified burner will be provided by Burnham.
2. If adapter is provided by Burnham, open carton
and remove contents. Apply four (4) small dabs
of silastic on rear surface of adapter plate to
temporarily hold gasket in place. Hold adapter plate
in position against burner swing door, align holes
and secure with four (4) 3/8” lock washers and
3/8” - 16 x 7/8” lg. cap screws.
3. If adapter is furnished with burner, follow
manufacturer’s instructions using gasket material
and hardware provided with burner.
4. USE A HOLE SAW OR KNIFE TO CUT BURNER
SWING DOOR INSULATION TO MATCH
HOLE SIZE ON BURNER ADAPTER PLATE.
After cutting, remove any and all loose pieces of
insulation which may become lodged or interfere
with the head of the burner air tube after insertion.
5. Secure burner to adapter plate with four (4) ½” lock
washers and four (4) ½” - 13 hex nuts provided.
Figure 6: Burner Adapter Plate Options
Boiler Model
Part No.
I.D.
No.
‘A’
‘B’
MPC4 thru MPC7
602263401
40
7-1/2
10-1/4
MPC8 thru MPC14
602263411
41
9
12
MPC15 thru MPC18
602263421
42
10-3/8
14-1/8
Power Flame (‘C’ Series) Burner Adapter Plate
Boiler Model
Part No.
I.D.
No.
‘A’
‘B’
MPC4 thru MPC7
602263451
45
6-3/8
10-1/4
MPC8 thru MPC11
602263461
46
8-3/8
11-11/16
Power Flame (‘JR’ Series) Burner Adapter Plate
Boiler Model
Part No.
I.D.
No.
‘A’
‘B’
MPC4 thru MPC7
602263001
00
6-3/4
10
MPC8 thru MPC15
602263011
01
8-1/4
10
MPC16 thru MPC18
602263021
02
10-1/4
11
Beckett (‘CF’ Series) Burner Adapter Plate
Boiler Model
Part No.
I.D.
No.
‘A’
‘B’
MPC4 and MPC5
602263031
03
5
10
MPC6 and MPC7
602263041
04
6
10
MPC8 thru MPC11
602263071
07
7-1/4
10
MPC12 thru MPC18
602263081
08
8-1/8
11
Beckett (‘CG’ Series) Burner Adapter Plate
CAUTION
Failure to properly fill all gaps between the
insulation and burner blast tube may result in
damage to the burner.
6. Confirm that hole in insulation fits snugly around
burner blast tube. If hole is oversized, open burner
swing door (with burner attached) to access burner
blast tube. Use additional fiberglass rope gasket
provided with burner to fill in any space between
insulation and blast tube. If additional rope gasket
is not provided with the burner, use 3/8” fiberglass
rope rated for 2300°F (provided by others).
When finished, close burner swing door and secure
hardware.
P.
Connect Internal Control / Safety Circuit Wiring
Harness to Burner Controls, see Figures 25 and 37.
Also, refer to Burner Installation Manual and wiring
diagrams provided with burner.
Содержание MPC
Страница 19: ...19 Figure 5 Manual or Hydraulic Draw up Section Assembly ...
Страница 28: ...28 Table VII Modular Return Water Mixing Tube RWMT RC ...
Страница 29: ...29 Figure 13 Return Water Mixing Tube RC Assembly and Installation ...
Страница 78: ...78 Figure 56 MPC Common Bare Boiler Components ...
Страница 80: ...80 Figure 56 MPC Common Bare Boiler Components continued ...
Страница 82: ...82 Figure 57 MPC Front Center Section Frame Rail Assembly ...
Страница 84: ...84 Figure 58 MPC Rear Section Frame Rail Assembly ...
Страница 86: ...86 Figure 59 MPC Return Water Mixing Tube RC Assembly ...
Страница 88: ...88 Figure 60 MPC Heat Exchanger Insulation Wrapper ...
Страница 90: ...90 Figure 61 MPC Internal Wiring Harness Components ...
Страница 92: ...92 Figure 62 MPC Jacket Panel Assembly ...
Страница 94: ...94 Figure 62 MPC Jacket Panel Assembly continued ...
Страница 96: ...96 Figure 63 MPC 2 nd and 3 rd Pass Flueway Baffles ...
Страница 98: ...98 Figure 64 MPC Standard 50 PSI Trim Control with 30 PSI and 80 PSI Working Pressure Trim Options ...
Страница 100: ...100 Figure 64 MPC Standard 50 PSI Trim and Control with 30 PSI and 80 PSI Working Pressure Trim Options continued ...
Страница 102: ...102 Figure 65 MPC Optional Controls ...