The catalytic converter needs heat to work, therefore before you start
testing, the fire must have been lit and burning on full for at least 15
minutes.
There are two tests to carry out. A Co / CO² ratio test and a room centre CO test.
1.
The first test is the CO / CO² ratio test and should be carried out at the fire exhaust vent,
do not stick the probe of the analyser through the grill but move the probe back and forth
1 inch in front of the outlet grill. (We use a piece of perforated 8mm pipe attached to the
analyser with flexible rubber tube). You should record a ratio of
no more than 0.002 %
(20ppm CO to 1% Co²). It is advisable to have a high sample of CO² as this will improve the
test.
2.
The second test is the room centre CO test. You should stand in the room centre with the
probe at waist height and read the level of CO. This should be
no more than 9ppm
over
ambient peak. Please record these readings on the customers guarantee card.
9.1
Oxygen Depletion Pilot System
This is a highly sensitive oxygen depletion sensor and
may not light first time or may extinguish after a few minutes, please advise the
customer of this. If any part of the Oxypilot is damaged the entire unit must be replaced.
Do not attempt to bend or alter the flame head, thermocouple or aeration hole. Use
only genuine spare parts as similar looking parts from other appliances may well give
different or inferior performance and could lead to a hazard.
9.2
Thermostat
A room temperature thermostat is provided (where applicable). It is set for
a normal range of operating temperatures (13
o
c
– 45
o
c
) but for more accurate
monitoring of room temperature it is advised that the sensing bulb is removed from the
fire and carefully moved to a cooler location up to 1 metre away, taking care not to
break or pinch the capillary tube. We recommend that the sensing bulb is moved from
the right hand side of the fire to the left and clipped to the gas inlet pipe.
9.3
Firefronts
The design of these affect combustion, therefore only the correct front
supplied with the appliance may be fitted.
9.4
Brief the customer on the operation of the appliance and give them all the instructions.
The customer must be told of the need for regular servicing of the appliance, this will be
at least once a year and must be made aware that no rubbish is to be thrown onto the
fire bed. The customer must also be made aware that the purpose provided ventilation
should be checked regularly and must not be blocked or restricted.
9.5
Completion of Warranty Card. The installer section of the guarantee card must be
filled in fully to validate the warranty. I.e. pressure, model, room size and Gas Safe™
registered installer (formerly CORGI) Number
If you have any questions or the fire is not operating correctly, phone the Burley help-
line BEFORE you leave the installation.
If the appliance is not fitted in strict accordance with these instructions, Burley cannot
be held responsible for any damage caused and reserve the right to charge for any
corrective work. Double check standing and working pressures and securely seal all
open chimneys and flues.