Installation
7
Logano plus SB615 - Technical specifications are subject to change without prior notice.
18
7.4
Boiler jacket
SB615/145 to 400 boilers
4 top panel sections
SB615/510 to 640 boilers
5 top panel sections
z
Position top panel sections loosely on side panels at
each side.
Fig. 18
Sealing the gap between burner and insulation.
Refractory may have to be cut to size depending on
burner make and model.
Item 1: Gap between burner tube and insulation
1
7-5/16"
(185)
USER NOTE
Follow the burner manufacturer’s instruc-
tions when fitting the burner.
The appropriate burner plate must be
used/modified according to the make/model
of the burner.
The gap between the burner tube and the
thermal insulation must be sealed by the in-
staller (Fig. 18).
Refractory is supplied with the boiler. It must
be cut to the right size to fit.
Fig. 19
Fitting boiler top panel sections – general principle
Item 1: Cutout on SB615/400 and up.
1
USER NOTE
On the SB615/400 and larger boilers, the
second top panel section has a cutout
(Fig. 19, Item 1); the rear sections are iden-
tical and are positioned with the flanged
edge to the front.