Boiler Installation
6
Logano plus SB615 - Technical specifications are subject to change without prior notice.
10
6
Boiler Installation
It is useful if there is a waste water drain near the installa-
tion site. Refer to page 29 for information on transporting
the boiler.
The boiler should be placed on a foundation
approx. 2 - 4" (50 - 100 mm) high. Refer to dimensions B
and L (Tab. 4) for sizing the foundation.
The base must be flat and level and able to support the
boiler gross weight.
Observe the recommended minimum clearances
(indicated in brackets) for installation and servicing when
positioning the boiler (Fig. 2 or Tab. 4).
The boiler body must be aligned horizontally.
Tab. 4
Wall clearances
1)
Take burner size account
Fig. 2
Boiler room (for dimensions see Tab. 4)
*
)
Take burner size into account.
32" *
min. 4
”
min. 8”
Recommended and minimum wall clearances in inch (mm)
Boiler
rating
Clearance
A
1
Clearance
A
2
1)
Lengh
L
Width
B
Width/Height
Delivered
recomm
inch (mm)
145
36" (914)
72" (1829)
72" (1816)
36" (900)
29" (720)
53" (1340)
minimum
inch (mm)
24" (610)
48" (1290)
recomm
inch (mm)
185
36" (914)
72" (1829)
72" (1816)
36" (900)
29" (720)
53" (1340)
minimum
inch (mm)
24" (610)
48" (1219)
recomm
inch (mm)
240
36" (914)
72" (1829)
73" (1845)
38" (970)
32" (790)
54" (1370)
minimum
inch (mm)
24" (610)
48" (1219)
recomm
inch (mm)
310
36" (914)
72" (1829)
73" (1845)
38" (970)
32" (790)
54" (1370)
minimum
inch (mm)
24" (610)
48" (1219)
recomm
inch (mm)
400
36" (914)
72" (1829)
73" (1845)
38" (970)
32" (790)
62" (1570)
minimum
inch (mm)
24" (610)
54" (1372)
recomm
inch (mm)
510
42" (1067)
78" (1981)
78" (1981)
44" (1100)
37" (920)
69" (1730)
minimum
inch (mm)
36" (914)
60" (1524)
recomm
inch (mm)
640
42" (1067)
78" (1981)
78" (1981)
44" (1100)
37" (920)
69" (1730)
minimum
inch (mm)
36" (914)
60" (1524)