Heating system servicing
Logano GB125 BE US/CA - Technical specifications are subject to change without prior notice.
44
Cleaning the condensate collector
V
Open the condensate collector clean-out cover [1].
V
Remove condensate residues.
V
Securely replace the condensate collector clean-out
cover [1].
Fig. 44 Cleaning the condensate collector
1
Clean-out cover
8.5
Cleaning the neutralizer unit and trap
The procedure for cleaning the neutralizer unit is
described in a separate instruction manual.
V
Disconnect the condensate pipes from the trap.
V
Remove deposits in the trap and refill with water.
V
Refit the condensate pipes.
Warning:
Risk of injury from acid burning!
The condensate in the condensate collector
and the trap can reach a pH level of 2.
V
Always wear suitable clothing and protec-
tive goggles when cleaning.
Warning:
Danger of life from flue gas poi-
soning!
A dry siphon or leaky condensate connec-
tions can release flue gases into the building.
V
Check the siphon fluid level regularly and
fill with water if needed.