Product description
Logano GB125 BE US/CA - Technical specifications are subject to change without prior notice.
12
2.7.2
Boiler room and ambient conditions
2.7.3
Fuel conditions
2.7.4
Power supply conditions
2.7.5
Hydraulic conditions and water quality
Operating conditions
Notes – Requirement in greater detail
Temperature in the boiler room
+40 to +104 °F
relative humidity
max. 90 %
No condensation or precipitation inside the boiler room
Dust/airborne particles
−
Excessive dust inside the boiler room must be avoided when the boiler is opera-
ting, e.g.:
– dust from building work
Combustion air supplied from outside must not be excessively loaded with dust
or airborne seed; if necessary, air filters should be fitted to prevent this:
– Air supply contaminated with dust from dirt roads and paths.
– Air supply contaminated with dust from production and processing facilities, e.g. quar-
ries, mines, etc.
– Airborne particles from thistles and similar
Halogenated-hydrocarbon com-
pounds
−
The combustion air must be free from halogen-hydrocarbon compounds.
– Identify the source of halogen-hydrocarbon compounds and seal it off. Where this is
impossible, route combustion air from areas that are not contaminated by halogenated-
hydrocarbon compounds.
Small animals
−
Prevent small animals from entering the boiler room, particularly through the air inlet vents –
by fitting them with screens.
Fire safety
−
Maintain clearances between the boiler and flammable materials in accordance with local
regulations. A minimum clearance of 16” is required. Never store flammable materials or liq-
uids in the vicinity of the boiler.
Flooding
−
In case of an acute risk of flooding, disconnect the boiler in time from the from its fuel and
power supply before water enters the room. Any general and burner components or control
equipment, which come into contact with water, must be replaced before re-commission-
ing.
Tab. 5
Boiler room and ambient conditions
Country
All countries
Fuels
#2 Fuel oil ASTM D396-05 Type 2
Approved for B5 Fuel Oil (5% biodiesel (B100) according ASTM D6751)
Remarks
The burner may only be operated with the specified fuel.
Clean and service once a year. Check that the entire system functions properly at the same time. Immediately rec-
tify any faults identified.
Tab. 6
Country-specific fuels and remarks
Operating conditions
Notes – Requirement in greater detail
Mains supply voltage
110 - 120 V
The outer casing/boiler must be grounded for safety reasons and in order to function correctly.
Circuit breaker
10 A
Frequency
60 Hz
Enclosure rating
−
IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø (> 1 mm Ø ),
no water proofing)
Tab. 7
Power supply
Operating conditions
Notes – Requirement in greater detail
Operating pressure (above
atmospheric)
15 – 44 psi
Maximum 30 psi with the supplied safety valve.
Permissible testing pressure
45 – 58 psi
Safety temperature limitation by
TR temperature control
122 – 194 °F
Safety temperature limitation by
manual reset high limit (STB)
212 °F
Water quality
−
The heating system may only be filled and topped up with water of domestic water quality.
We recommend a pH level of 8.2 – 9.5.
Tab. 8
System configuration and water quality