Product description
Logano GB125 BE US/CA - Technical specifications are subject to change without prior notice.
10
2.6
Dimensions and specifications
2.6.1
Logano GB125 BE dimensions
Fig. 3
Connections and dimensions (measurements in inches)
VK
= Boiler supply
RK
= Boiler return
EL
= Boiler drain (connection for drain valve)
Dimensions and connections:
Boiler model
Unit
GB125/22 BE
GB125/30 BE
GB125/35 BE
Boiler sections
3
4
4
Rated heat output (gross output)
131/86 °F
MBtu/hr
76
102
124
Rated heat output (net IBR rating)
131/86 °F
MBtu/hr
67
90
109
Rated heat output (gross output)
176/140 °F
MBtu/hr
75
100
121
Rated heat output (net IBR rating)
176/140 °F
MBtu/hr
65
87
105
Burner input
MBtu/hr
81
108
131
AFUE
%
91.2
91.1
91.0
Flue gas temperature 176/140 °F
°F
176
176
192
Boiler water content
gal
8.7
11.8
11.8
Gas volume of combustion chamber and heat
exchanger
cu.ft.
1.5
2.0
2.0
Oil firing rate
gph
0.60
0.75
0.95
Flue gas back-pressure
in. W.C
.
0.08" - 0.14" W.C.
Heat exchanger water pressure loss
(DeltaT = 18 °F)
ft. of
head
1.8'
2.0'
2.7'
Maximum supply temperature
1)
1) Safety manual reset high limit (safety temperature limiter, STB)
Maximum permitted supply temperature = Safety limit (STB) – 32
°F
Example: Safety limit (STB) = 212
°F
, maximum possible flow temperature = 212 - 32 = 180 °F
The safety limit must meet the national regulations of the country concerned.
°F
212
Maximum operating pressure
psi
44
Maximum time constant of thermostat and
high limit safety cut-out (STB)
s
40
Tab. 2