8
Connecting the boiler on the flue gas side
Logano G515 – 6 720 647 208 (2014/09)
31
8
Connecting the boiler on the flue gas side
This chapter explains how to connect the boiler on the flue gas side.
8.1
Fitting the vent pipe sealing collar (accessory)
▶ Push the vent pipe (
Fig. 59, [4]) as far as possible onto the draft
diverter outlet (
Fig. 59, [6]).
▶ Place the vent pipe sealing collar (
Fig. 59, [1]) around the vent
pipe (
Fig. 59, [4]) and draft diverter (
Fig. 59, [6]) outlet so
that it overlaps at the top.
▶ Place hose clamps (
Fig. 59, [5]) over the vent pipe sealing collar
(
Fig. 59, [1]). One of the hose clamps (
Fig. 59, [5]) must
press onto the draft diverter outlet (
Fig. 59, [6]) and and one
onto the vent pipe (
Fig. 59, [4]).
▶ Tighten hose clamps (
Fig. 59, [5]). The vent pipe sealing collar
(
Fig. 59, [1] must fit smoothly and firmly in place.
Fig. 59 Installing the vent pipe
[1]
Vent pipe sealing collar
[2]
Flue gas temperature sensor
[3]
Sleeve
[4]
Vent pipe
[5]
Hose clamps
[6]
Exhaust manifold
[A]
2 × Vent pipe diameter, at least 28 – 22/64 inches (720 mm)
8.2
Installing a flue gas temperature sensor (accessory)
▶ Weld a sleeve (
Fig. 59, [3]) at a distance of 2 × vent pipe
diameters (A) from the draft diverter (
Fig. 59, [6]) in the vent
pipe (
Fig. 59, [4]).
▶ Fit the flue gas temperature sensor (
Fig. 59, [2]) as described in
the separate installation manual.
We recommend you use a vent pipe sealing collar
(
Fig. 59, [1]).
Retighten the hose clamps if required.
)
6 720 642 623-57.1o
6
4
1
3
2
5