6
Positioning the boiler
Logano G515 – 6 720 647 208 (2014/09)
12
6.2
Recommended wall clearances
Fig. 6
Installation room with boiler
The burner door can be right or left hung/opening (the boiler is always
supplied with the door attached on the right).
When installing your boiler maintain the recommended minimum
dimensions. Select the recommended clearances between wall and
boiler for easy access for installation, maintenance and service work.
The wall clearance on the hinge side must be at least the burner
projection (AB). A distance of AB + 3 – 15/16" (AB + 100 mm) from the
wall is recommended.
If you do not observe the recommended minimum clearance (
Fig. 6),
you will not be able to use the cleaning kit (accessory). Alternatively,
shorter cleaning devices or wet cleaning may be used. Alternatively
shorter cleaning devices or wet cleaning may be used.
6.3
Installing the boiler on a boiler base or foundation
Fig. 7
Base dimensions (dimensions in inches (mm))
If this boiler base is not used, a concrete foundation can be constructed
on-site. When building the base, a
3 – 15/16 × 1 – 31/32 × 5/16 inches (100 × 50 × 8 mm) steel angle
or 3 – 15/16 × 13/64 inches (100 × 5 mm) steel flat should be
incorporated, to ensure that the boiler sections can slide when the boiler
is installed (
Fig. 7 and Tab. 10).
It is advisable to place the boiler on a 2 – 4 inch (50 – 80 mm) tall base
(
Fig. 7, [1]). The installation area must be completely flat and level.
The front edge of the boiler should be flush with the edge of the base.
Observe the recommended wall clearances for complete
opening of the burner door, for boiler installation and for
cleaning and maintenance (
Fig. 6 and Tab. 9).
Boiler capacity
Clearance A in inches (mm)
MBH (kW)
Boiler
sections
Recommended
minimum
819 – 1.194
(240 – 350)
7 – 9
66 –15/16" (1700) 39 – 3/8" (1000)
1,365 – 1,740
(400 – 510)
10 – 12
86 – 39/64" (2200) 39 – 3/8" (1000)
Table 9
6 720 642 623-04.1o
L
K
(400 mm)
≥ 15 3/4"
(980 mm)
38 37/64"
(AB+100 mm)
AB + 4"
AB
A
(~ 900 mm)
35 1/2"
15-3/4"
38-9/16"
35
-1
/2
"
A silencing boiler base is available as an accessory from
Buderus.
When building the bases, consider to which side the
burner swings out (left or right-hand burner door stop
(
Fig. 6, page 12).
Number of boiler
sections
L1
(base) in inch (mm)
L2
(steel section) in inch (mm)
7
53 – 35/64 (1360)
46 – 27/32 (1190)
8
60 – 15/64 (1530)
53 – 35/64 (1360)
9
66 – 59/64 (1700)
60 – 15/64 (1530)
10
73 – 5/8 (1870)
66 – 59/64 (1700)
11
80 – 5/16 (2040)
73 – 5/8 (1870)
12
87 (2210)
80 – 5/16 (2040)
Table 10
6 720 642 623-05.1o
L
2
(540 mm)
(~ 90 mm)
(100 mm)
(850 mm)
(~ 50...80 mm)
2...4"
L
1
33 1/2"
1
3 1/2"
4"
21 1/4"
33-1/2"
21-1/4"
3-1/2"