9
Installing the control panel
Logano G515 – 6 720 647 208 (2014/09)
32
9
Installing the control panel
This section explains how to install a Logamatic 4000 series control
panel and its set of temperature sensors.
9.1
Installing the control panel
Fig. 60 shows the control panel and the top cover “A” from the back.
▶ Loosen both screws on top of the control panel (
Fig. 60, [1]) and
remove the top cover.
▶ Mounting the control panel in place Fit the control panel at the front
by inserting the alignment tabs (
Fig. 60, [4]) into the oval holes in
the front top boiler cover (
Fig. 60, [5]). Tilt the control panel
forward and then tip backward. The flexible hooks (
Fig. 60, [2])
must engage with the rectangular cutouts in the rear of the front
boiler cover (
Fig. 60, [3]).
▶ Attach the base of the control panel to the top cover (
Fig. 60, [6])
using two self-tapping screws (
Fig. 60, [7]).
Fig. 60 Installing the control panel
9.2
Fitting temperature sensor assembly and burner
cable
▶ If necessary, make knock-outs (
Fig. 61, [1]) in the rear panel of
the cable entry (Logamatic 33xx) or remove the rear panel section
(Logamatic 43xx) (
Fig. 61, [2]).
▶ Route the capillaries through the cable entry and unroll to the
required length.
Fig. 61 Preparing the cable entry
The sensor well has already been sealed in the flow connection socket
(
Chapter 7.5, page 18).
The temperature sensor set connected to the control panel (consisting
of three temperature sensors and one sensor blind piece
Fig. 62,
[1]) is installed in the sensor well R ¾.
▶ Route capillary pipe sensor to the measuring port of the boiler and
then guide the sensor into the sensor well (
Fig. 62, [2]) and
secure with the retaining clip (
Fig. 62, [3]).
Fig. 62 Installing the temperature sensor assembly
▶ Screw cable entry (
Fig. 63, [1 and 2]) to the left and right of the
rear boiler panel.
A permanent connection must be made in accordance with EN 50165 or
the relevant national installation standard.
Observe the following when connecting the control
panel:
▶ Lay out cables and capillaries carefully.
▶ Do not bend the capillaries during installation.
▶ Never carry out any electrical work on the heating
system unless you are licensed for this type of work.
If you are not suitably qualified, arrange for a
qualified electrician to make the electrical
connections.
▶ Observe the local regulations!
1
2
4
5
6
3
7
6 720 615 362-18.2O
6 720 642 623-58.1o
1
2
6 720 642 623-59.1o
1
2
3
Содержание Logano G515
Страница 66: ...Appendix Logano G515 6 720 647 208 2014 09 66 ...
Страница 67: ...Appendix Logano G515 6 720 647 208 2014 09 67 ...
Страница 68: ......