10
Mounting the burner
Logano G515 – 6 720 647 208 (2014/09)
34
10
Mounting the burner
This chapter explains the basic steps involved in fitting a burner
▶ Close the burner door and seal with 4 machine screws (M16 × 140)
(
Chapter 7.8.3, page 21, Fig. 32, [3 to 6]). Tighten the machine
screws evenly crosswise.
If you have ordered an undrilled burner plate, you will have to machine
the plate on site:
▶ Drill or cut the burner plate (
Fig. 66, [1]) to match the required
burner tube diameter Ø 10 – 5/8 inches (270 mm).
▶ Drill burner attachment holes using the burner flange as a template.
▶ Screw burner plate onto the burner door (seal with GP sealant rope;
diameter Ø 25/64 inches (10 mm)).
▶ Screw the burner to the burner plate.
▶ Cut out insulating rings to match the burner tube diameter
(
Fig. 66, [2]).
▶ Fill the remaining gap between the burner door thermal insulation
and the burner tube
Fig. 66, [4]) using the appropriate insulating
rings (
Fig. 66, [3]).
▶ Connect the vent connection to the burner to ensure the inspection
window remains free of deposits.
Fig. 66 Mounting the burner
NOTICE:
Risk of system damage from use of incorrect
burner.
▶ Only use burners that meet the technical
requirements of the oil/gas-fired boiler Logano
G515 (
Chapter 3, page 8).
You can obtain undrilled or predrilled burner plates (hole
pattern depends on burner) as accessories from
Buderus.
6 720 642 623-63.1o
2
3
4
1
(145 mm)
5 45/64"
5-4
5/6
4"
Содержание Logano G515
Страница 66: ...Appendix Logano G515 6 720 647 208 2014 09 66 ...
Страница 67: ...Appendix Logano G515 6 720 647 208 2014 09 67 ...
Страница 68: ......