7
Boiler block assembly
Logano G515 – 6 720 647 208 (2014/09)
20
7.7
Boiler water connections
Please observe the following information regarding the boiler
connection to the system side. These instructions are important for
trouble-free operation.
The weld neck flange is fitted to the upper boiler hub (
Fig. 28, [3] –
return connection) if the return is connected at a later stage.
The weld neck flange and flat gasket are shown (
Fig. 28, [4 and 5]).
▶ The supply connection flange (
Fig. 28, [1]) with flat gasket
(
Fig. 28, [2]) is required for connecting the supply at a later
stage.
Fig. 28 Fitting a flange
7.8
Installing draft diverter, baffles and burner door
Next step in the assembly process is to install the burner door and draft
diverter. The pre-assembled boiler comes with these components
already installed.
7.8.1
Positioning the draft diverter
The GP sealant rope (fiberglass cord with silicon casing) which forms a
seal is inserted in the draft diverter at the factory.
▶ Place the draft diverter onto the four threaded studs on the rear
section (
Fig. 29 [1 to 4]) and secure using washers and nuts.
Fig. 29 Fitting the draft diverter
7.8.2
Screwing cleanout cover onto rear section
If the cleanout covers have been removed in order to attach the
installation aid to the rear section:
▶ Screw the cleanout covers with washers and nuts back onto the rear
section (
Fig. 30, [1 and 2]).
Fig. 30 Fitting the cleanout cover
NOTICE:
Risk of system damage from leaking
connections.
▶ All pipe connections to the boiler must be free of
stress and tension.
NOTICE:
System damage from deposits, local
overheating, and corrosion.
▶ As a basic rule, clean and flush existing systems
thoroughly before connecting the new boiler.
▶ Install a desludging unit in the boiler return to
prevent damage to the boiler.
The boiler supply and return manifolds are included in
the Buderus scope of delivery.
NOTICE:
Risk of system damage from temperature
stresses.
▶ Install a fill valve on the system side.
▶ When the heating system is in operation, do not fill it
via the boiler fill & drain valve. Instead, use the fill
valve on the system side.
6 720 642 623-28.1o