9- 38
Service Guide
LWE180, LWE200, LPE200, LPE240
© BT Europe AB
Electrical System – 5000 LWE 180/200 LPE 200
Parameters
T-code
Valid from serial number
Date
Order number
660, 661, 662, 497
723984-
2005-05-11
225553-040
Independent variable #0 = 4:Activate the main contactor controlled by the spider’s digital input
0:Spider 0
1:Spider 1
0-7:Digital input 1-8
0-30:Holding time 0-
30 minutes
Not used
Independent variable #0 = 5: Lift/lowering controlled by the spider’s digital inputs
0:Spider 0
1:Spider 1
0: Lift, digital input 1
Lowering, digital
input 2
Blocking of lower-
ing, input 3
1: Lift, digital input 2
Lowering, digital
input 3
Blocking of lower-
ing, input 4
2: Lift, digital input 3
Lowering, digital
input 4
Blocking of lower-
ing, input 5
3: Lift, digital input 4
Lowering, digital
input 5
Blocking of lower-
ing, input 6
4: Lift, digital input 5
Lowering, digital
input 6
Blocking of lower-
ing, input 7
5: Lift, digital input 6
Lowering, digital
input 7
Blocking of lower-
ing, input 8
0: Blocking of lower-
ing disconnected
1: Blocking of lower-
ing connected
0: Fork lift/lowering
1: Support arm lift/lower-
ing
Independent variable #0 = 6:Lift height limitation with by-pass
0:Spider 0
1:Spider 1
0-7: Limit
switch for
digital input 1-8
1-6: By-pass,
option switch 1-6
Not used
Table 2: List of configurable optional functions
Independent
variable #1
Independent vari-
able #2
Independent var-
iable #3
Independent varia-
ble #4