Commissioning
B 3
ekrPro Com
60
web guide controller
EDV No.:
MD.191.01.05/1.6.x Chapter:
B 3
with analog sensors
Date:
23.11.2007
Page:
11/73
B 3.5.3 Setting the actuator
guiding direction
For standard systems, the EMS17 is registered as the actuator.
The direction has to be set for it.
1. Select the sub-directory
Direction
from the menu
Actuator
.
Confirm the selection by pressing ENTER.
If necessary, the actuator guiding direction for manual mode
can be reversed by activating the checkbox
Mot. Dir. Inverted
.
The rotational direction can be checked on the spot.
Drive the actuator using the
F2
or
F3
key.
If key
F2
is pressed, the actuator must move the material web
in the direction of sensor 1, if
F3
is pressed it must move it
towards sensor 2!
Pressing
F2
or
F3
automatically changes the controller to
“manual” operating mode.
The sensor allocation can be checked on the spot. Press the
MENU
button. The operating display is shown.
Cover one sensor. The change to the coverage range shows
the allocation.
After this, press the
MENU
key to ENTER to the settings
menu.
2. Press the
ESC
button to exit the window.
B 3.5.4 Setting the actuator
path limits
From here it is possible to limit the adjustment travel of the
actuator.
1. Select
Actuator
in
General Setup
, then the sub-directory
SC-Component
and finally
Pos. Limit
.
Confirm the respective selection by pressing ENTER.
2. Use the vertical arrow keys to deactivate the checkbox
active
.
This deactivates the function of both limit switches.
The settings can
only be entered in the deactivated state.
3. Use the
F2
key to drive the actuator until it reaches the
required left limit switch position.
The actual position of the actuator supplied by the position
feedback is shown in the middle above the
F2
and
F3
keys.
4. Confirm this position by pressing the
F1
key.
The limit switch position is stored.
The corresponding position value is shown below the
checkbox.
123
456
789
0
Change User
Material Setup
Sel. Std. System
opt. Logic
General Setup
Actuator
Sensors/EFE
Control Loop
FVG
Type (EMS&Hydr.)
Hydraulics Add-on
Directions
SC-Transducer
Type & Dir.
SC W & XP
Pos. Limit
Toggle Man Dir. until
F2 moves to sensor 1
Mot. Dir. Inverted