Commissioning
B 3
ekrPro Com
60
web guide controller
EDV No.:
MD.191.01.05/1.6.x Chapter:
B 3
with analog sensors
Date:
23.11.2007
Page:
9/73
Choose standard system …
… & press F2 to activate
select a standard config.
Set.
De f.
F1 for fa ct. defaults
Choose standard system …
… & press F2 to activate
select a standard config.
Set.
De f.
F1 for fa ct. defaults
B 3.5 Commissioning standard system
To simplify commissioning, the commissioning staff can select his
own system from a list of the most common standard systems listed
under the menu
Sel. Std. System
.
Following the selection, all of the basic settings are automatically
entered in the setup menu and the system is switched to the
operating mode
MAN
.
B 3.5.1 Select standard system
1. Press the
MENU
button.
The setup menu of the controller appears in the display.
2. Select menu "Sel. Std. System“ and press ENTER.
3. The selection window for the standard system will appear.
4. Press the ENTER button.
The option list opens with the most common standard
systems. Individual entries each contain the following
information:
5. Use the vertical arrow keys to select the system that matches
the present system.
Confirm the selection with the ENTER key.
The selected system is displayed.
6. To import the standard system configuration, press
function key
F2
(set.)
.
The selection is confirmed by the message window
Standard
System Set
.
The base settings in the setup menu are automatically
entered by the system.
After this, the selection window is displayed again.
7. Press the
ESC
button to exit the window.
Attention!
After selecting the standard system, adjustment for a
particular application (e.g. material properties) must
take place.
Accordingly, the following steps should be carried out:
Type of connected
sensor(s)
Type of connected
actuator
Type of the
sensor positioning device
(if fitted)