CONVENIENCE OUTLETS
Convenience Outlets
Two types of convenience outlets are offered on 547K models:
non-powered and unit-powered. Both types provide a 125 vac
ground-fault circuit-interrupt (GFCI) duplex receptacle rated at
15A behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 28.
Fig. 28 — Convenience Outlet Location
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory installed
convenience outlets is now required by UL standards. This
cover cannot be factory-mounted due to its depth. The cover
must be installed at unit installation. For shipment, the conve
-
nience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box.
The kit includes the hinged cover, a backing plate and gasket.
NOTE: DISCONNECT ALL POWER TO UNIT AND CONVE
-
NIENCE OUTLET. Use approved lockout/tag-out procedures.
1. Remove the blank cover plate at the convenience outlet;
discard the blank cover.
2. Loosen the two screws at the GFCI duplex outlet, until
approximately
1
/
2
-in. (13 mm) under screw heads is exposed.
3. Press the gasket over the screw heads. Slip the backing
plate over the screw heads at the keyhole slots and align
with the gasket; tighten the two screws until snug (do not
over-tighten).
4. Mount the weatherproof cover to the backing plate as
shown in Fig. 29.
5. Remove two slot fillers in the bottom of the cover to per
-
mit service tool cords to exit the cover.
6. Check cover installation for full closing and latching.
Non-Powered Type
This type requires the field installation of a general-purpose
125-v 15-A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting wire
size, fuse or breaker requirements and disconnect switch size
and location. Route 125-v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Fig. 29 — Weatherproof Cover Installation
Unit-Powered Type
A unit-mounted transformer is factory-installed to step-down
the main power supply voltage to the unit to 115-v at the du
-
plex receptacle. This option also includes a manual switch with
fuse, located in a utility box and mounted on a bracket behind
the convenience outlet; access is through the unit’s control box
access panel. See Fig. 28.
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is a
customer option. If local codes permit, the transformer primary
leads can be connected at the line-side terminals on a unit-
mounted non-fused disconnect or Heating, Air Conditioning
and Refrigeration (HACR) breaker switch; this will provide
service power to the unit when the unit disconnect switch or
HACR switch is open. Other connection methods will result in
the convenience outlet circuit being de-energized when the unit
disconnect or HACR switch is open. See Fig. 30.
Fig. 30 — Powered Convenience Outlet Wiring
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status
before opening unit for service. Locate its disconnect
switch, if appropriate, and open it. Lock-out and tag-out
this switch, if necessary.
CONVENIENCE
OUTLET GFCI
PWD-CO FUSE
SWITCH
PWD-CO
TRANSFORMER
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
GASKET
GFCI RECEPTACLE
NOT INCLUDED
TOP
TO
P
TOP
WET LOC
ATIONS
W
E
T
L
O
C
A
TI
O
N
S
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230
240
L1: RED +YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460
480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575
600
L1: RED
L2: GRA
H1
H2