Fig. 24 — Cooling Charging Chart - 5 Ton
Fig. 25 — Cooling Charging Chart - 6 Ton
COMPRESSOR
Lubrication
The compressor is charged with the correct amount of oil at the
factory.
Replacing Compressor
NOTE: Only factory-trained service technicians should remove
and replace compressor units.
48TC003783
A
SUCTION LINE TEMPERATURE [°F/°C]
-1.1
1.7
4.5
7.2
10.0
12.8
15.6
18.3
21.1
23.9
26.7
29.5
32.2
30
35
40
45
50
55
60
65
70
75
80
85
90
]
a
p
K /
gi
s
p[
E
R
U
S
S
E
R
P
N
OI
T
C
U
S
551
620
689
758
827
896
965
1034
1103
1172
1241
80
90
100
110
120
130
140
150
160
170
180
5 Ton 50FCQ / 547K / RHV
R410A Refrigerant Charging Chart
(Unit must be operated in cooling mode)
OUTDOOR
TEMP
°F / °C
115 / 46
105 / 41
95 / 35
85 / 29
75 / 24
65 / 18
55/ 13
45/ 7
6 Ton 50FCQ / 547K / RHV
R410A Refrigerant Charging Chart
(Unit must run in cooling mode, on high stage
compressors & outdoor fan on high speed)
Outdoor Coil Leaving Temperature, [°C/°F]
-6.7
4.4
15.5
26.6
37.7
48.8
59.9
20
40
60
80
100
120
140
Add Charge if Above the Curve
Remove Charge if Below the Curve
48TC003784
A
Compressor Discharge Pressure, [psig/Kpa]
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
150
200
250
300
350
400
450
500
550
600
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to com
-
ponents.
The compressor is in a R-410A refrigerant system and uses
a polyolester (POE) oil. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE oils can absorb
15 times as much water as other oils designed for HCFC
and CFC refrigerants. Avoid exposure of the oil to the
atmosphere.
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Never use air or gases containing oxygen for leak testing or
for operating refrigerant compressors. Pressurized mixtures
of air or gases containing oxygen can lead to an explosion.
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Never use non-certified refrigerants in this product. Non-
certified refrigerants could contain contaminates that could
lead to unsafe operating conditions. Use ONLY refrigerants
that conform to AHRI Standard 700.
CAUTION
INSTALLATION SITE DAMAGE
Failure to follow this caution can result in damage to
equipment location site.
R-410A refrigerant contains polyolester (POE) oil that can
damage the roof membrane. Caution should be taken to
prevent POE oil from spilling onto the roof surface.
The factory also recommends that the suction and discharge
lines be cut with a tubing cutter instead of using a torch to
remove brazed fittings.