4 Installing the pump controller
48
bplogic intelligent pump controller
18/02/2021
The M12 plug connections are allocated as follows:
Pin
X1
X2
X3
X4
X5
X6
1
+ 24 V
Sensor
+ 24 V
Sensor
+ 24 V
Actuator
+ 24 V
Sensor
+ 24 V
Sensor
+ 24 V
Actuator
2
Analog
In 1
Digital
In 1
Digital
Out 1
Analog
In 2
Analog
Out 1
Digital
Out 3
3
GND
Sensor
GND
Sensor
GND
Actuator
GND
Sensor
GND
Sensor
GND
Actuator
4
–
Digital
In 2
Digital
Out 2
–
–
Digital
Out 4
5
FE
FE
FE
FE
FE
FE
Observe the connection values:
Maximum allowed actuator supply current (total): 1.0 A