© 2020 Breckwell Hearth
11
INSTALLATION
air is to be used, you will need a pipe length (see
“COMBUSTION AIR SUPPLY”) equal to the chimney
height plus 12 inches.
2. Attach cerablanket wrap to the end of vent pipe that
will connect to the stove. Use 12-inch lengths of light
gauge metal wire (not included) or metallic tape (not
included). This is to protect interior components from
excess heat.
3. Set the insert on the hearth and slide it in far enough
to attach the vent pipe (and combustion pipe if used).
4. Attach flashing, route power cord out the side nearest a
120V receptacle. Slide in insert.
5. Measure and build chimney top. Cut out hole for vent
pipe (and combustion air intake pipe, if used). Install
and seal with a non-hardening mastic to prevent water
leakage. Install the vent cap.
TOP PLATE (SEAL TO
CHIMNEY TOP WITH
NON-HARDENING
MASTIC)
NOTE: FOLLOW METAL
CHIMNEY INSTALLATION
INSTRUCTIONS
FIREPLACE INSERT
SIDE ELEVATION
CHIMNEY NEED ONLY
EXTEND 12” ABOVE
BLANKING PLATE
(OPTIONAL BUT NOT
RECOMMENDED)
1” CERIBLANKET
3” OR 4”
STAINLESS
STEEL SINGLE
WALL PIPE
EXTENTION TO
CHIMNEY TOP
REQUIRED IN
MOBILE HOME &
ZERO-CLEARANCE
FIREPLACES.
RECOMMENDED IN
ALL FIREPLACES.
NOTE: IF
APPLICABLE L-VENT
CAN BE USED IN
PLACE OF FLEX PIPE
BLANKING PLATE
(SEAL WITH
NON-HARDENING
MASTIC)
OPTIONAL COMBUSTION AIR INTAKE (EXTENDS THROUGH CHIMNEY TOP WITH 180
DEG. BEND) REQUIRED IN MOBILE HOMES, NOT RECOMMENDED IN MASONRY, ZERO
CLEARANCE, OR BUILT-IN FIREPLACES
NOTE: WHEN MANTLE
EXTENDS MORE THAN 6”
FROM FIREPLACE FACE A
15” MIN. DIMENSION
MUST BE MAINTAINED
FROM STOVETOP TO
BOTTOM OF MANTEL
LEVELING BOLTS
12”
14” MIN.
C. WHEN VENT PIPE EXTENDS THROUGH CHIMNEY
BLANKING PLATE (Masonry Fireplaces Only)
1. You will need a pipe length that extends 12” above the
blanking plate. NOTE: This installation is optional but
not recommended. Outside combustion air cannot be
drawn from the chimney cavity in this installation.
2. Attach cerablanket wrap to that end of vent pipe that
will connect to the stove. Use 12-inch lengths of light
gauge metal wire (not included) or metallic tape. This is
to protect interior components from excess heat.
3. Measure and build blanking plate. Cut out hole for vent
pipe (and combustion air intake pipe, if used). Install
and carefully seal blanking plate with non-hardening
mastic. Failure to properly seal may result in smoke
spillage.
4. Slide vent pipe (and intake pipe if used) up through the
blanking plate hole, leaving enough to pull back down.
5. Set the insert on the hearth, adjust the leveling bolts on
the rear sides, and slide it in far enough to attach the
vent pipe (and combustion air pipe if used). Be sure to
seal where the pipe passes through the blanking plate.
6. Attach flashing), route power cord out the side nearest
a 120V receptacle. Slide in insert.
D. AS A BUILT-IN FIREPLACE
LISTED
CHIMNEY
CAP
6”
MIN
6”
MIN
27”
MIN
8”
MIN
6”
MIN
6”
MIN
20”
MIN
14”
MIN
3”
MIN
LISTED
THIMBLE
OPTIONAL
VERTICAL
INSTALLATION
LISTED L-VENT
CHIMNEY
SIDING
MANTLE
FACING
RAISED HEARTH MUST BE BUILT OF
8” HOLLOW CONCRETE BLOCKS
STORM COLLAR
LISTED CHIMNEY CAP
CHASE CAP
The figure describe the installation vented into either a special
chase built outside an outer wall or a false inside wall. This
is especially suited for new construction or remodeling.
The equipment compartment (sides and rear of the stove
in fireplace) must be enclosed per the applicable electrical
standards. NOTE: Floor protection for Built-in raised
hearths requires a continuous sheet beneath to prevent the
possibility of embers falling through to the combustible floor
if cracks or separation should occur in the finished surface.
The chase dimensions shown are minimums and must be
maintained.
Содержание SP24i
Страница 31: ...2020 Breckwell Hearth 31 NOTES...