Figure 12. Typical Horizontal Power Direct Vent System.
Vertical Installation
Vertical venting system
must be
supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe
length.
CAUTION
Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or
venting system.
Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used
to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or
high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.
Follow the following procedure for direct venting through the roof:
1. Cut the necessary holes through the roof and ceiling. Cut two 4 ½ inch
(11.4 cm)
diameter holes (for 4 inch (
10.2 cm
) diameter
pipe), or 6 ½ inch (
15.5 cm
) diameter holes (for 6 inch (
15.2 cm
) diameter pipe) in the ceiling and roof.
2. Install the exhaust vent and air intake plastic pipes as shown in Figure 13. Make sure that the installation meets the local codes
and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or CGA/CAN B149 Installation Code.
23