VENTING 

The venting instructions must be followed to avoid restricted combustion or recirculation of flue gases.  Such 

conditions cause sooting or risks of fire and asphyxiation. 

 

This water heater can be installed as either a power direct vent system or power vent (air from inside) system.  If it is 

installed as a direct vent system, then the air intake and the exhaust vent are piped to the outside.  If a power vented 

system is used, then air is drawn from inside and only the exhaust is piped to the outside.  Determine which system is 

best for your application and install as described in the following sections. 

 

VENT INTAKE/EXHAUST TERMINALS 

This water heater is supplied with a 4 inch (10.2 cm) diameter screened intake elbow and exhaust coupling referred to 

as the air intake terminal and the exhaust vent terminal.  These 4 inch supplied vent terminals can be used with 4 inch 

venting.  When venting with 6 inch (15.2 cm) venting is desired, please discard 4 inch vent terminals and use field 

supplied 6inch fittings instead.  It is recommended to use a galvanized ¼”x1/4” square opening screen cut to a 7 ½” 

diameter circle.  Then insert the screen into the field supplied intake/exhaust terminals. 

 

POWER DIRECT VENT INSTALLATION

 

Venting may be run horizontally through an outside wall or vertically through a roof through using either 4 inch 

(10.2 

cm)

 or 6 inch (15.2 cm) diameter pipe.  This water heater is supplied with a screened intake elbow and exhaust 

coupling referred to as the air intake terminal and the exhaust vent terminal.  

 

 

Power Direct Vent Terminal Location 

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.  Before the vent is 

installed, determine the vent pipe termination location as shown in Figure 11. 

 

 

 

CAUTION 

Check to make sure flue gases 

do not

 recirculate into the air intake terminal when using direct venting.  If the water heater is 

having service issues, flue recirculation may be a contributing factor.  Even when the minimum vent terminal separation 

distances are followed, recirculation may still occur depending upon the location outside the building, the distance from other 

buildings, proximity to corners, weather conditions, wind patterns, and snow depth.  Periodically check to make sure that flue 

recirculation is not occurring.  Signs of flue gas recirculation include frosted or frozen intake terminals, condensate in the intake 

terminal and venting system, oxidation or white chalk material on the flame sensor or spark rod.  Correction to flue recirculation 

may involve angling the intake away from the exhaust terminal, increasing the distance between them, relocating the air intake 

to another side of the building, or using inside air for combustion. Check to be sure the intake and exhaust terminals are not 

obstructed, especially during periods of below freezing weather. 

All intake and exhaust venting components 

must

 have the same diameter size.  

Do not

 use a different size on the intake and 

exhaust venting.  For 4 inch venting, use the supplied 4 inch vent terminals.  For 6 inch venting see the terminal section. 

Be sure the condensate runs freely to a drain and does not accumulate inside the water heater.  In cold climates, precautions 

may need to be taken to ensure that the condensate drain does not freeze.  Make sure the condensate trap or drain loop is 

installed to prevent flue gases from being discharged into the room.  Refer to the Venting section of the Installation and 

Operation Manual for complete instructions on venting and condensate drainage. 

High levels of dust and debris such as road and construction dust, insects, and tree pollen may clog the burner resulting in 

poor performance and damage to the water heater.  Avoid air intake locations where debris can be created such as exhaust 

ventilation hoods, gravel parking lots, and near outdoor spotlights that attract bugs.  For these installations, an air intake filter 

kit, part number 239-47330-00A, is available as an accessory service part from the installer of this water heater.  The air intake 

filter kit is not designed to filter out airborne contaminants or chemicals that may damage the water heater. 

    

CAUTION 

The vent shall terminate a minimum of 12 inches above expected snowfall level to prevent blockage of vent termination.

The horizontal centerline of the exhaust vent terminal (if applicable) 

must not

 be located lower than the horizontal 

centerline of the air intake terminal if vented through the same wall.

A service drain loop must be installed in the drain tubing to serve as a condensate trap to prevent flue gases from 

escaping into the room.   

DO NOT

 position the air intake above the exhaust terminal.

NEVER

 locate the air intake where exhaust gases can be introduced.

NOTICE 

The air intake and exhaust terminals may be located on separate outside walls or one terminal may exit the roof while 

the other is through the wall. The total combined equivalent vent length must be within the limits specified in the venting 

tables and the intake length cannot exceed the exhaust by more than 30 feet. The minimum recommended vent 

separation distance between the intake and exhaust terminals is 36”. Local conditions may require a need for greater 

vent separation distances.  

19

Содержание 120T400

Страница 1: ...S Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instru...

Страница 2: ...tion or in Canada CAN CGA B149 1 Natural Gas Installation Code Latest Edition or CAN CGA B149 2 Propane Installation Code Latest Edition The following terms are used throughout this manual to bring at...

Страница 3: ...elief valve is installed into the proper location at the top of this water heater It is the responsibility of the installing contractor to see that all controls are correctly installed and are properl...

Страница 4: ...air escaping through the pipes as hot water begins to flow Do not smoke or have open flame near the faucet at the time it is open WARNING Prior to connecting the gas supply line to a gas fired water h...

Страница 5: ...LBS 120T400 399 999 119 77 1 8 33 6 12 58 61 71 73 1 1 1 1 1120 120T500 499 999 119 77 1 8 33 6 12 58 61 71 74 7 8 1 1 1 1 1135 DIMENSIONS MILLIMETERS Model No Input Rate KW Storage Capacity Liter A...

Страница 6: ...serious personal injury and or death The temperature may be adjusted from about 100 F 38 C to about 180 F 82 C The thermostat was adjusted to 100 F 38 C before the water heater was shipped from the fa...

Страница 7: ...nally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Sh...

Страница 8: ...ng the water heater POWERED ANODE SYSTEM The powered anode system provides corrosion protection to the tank by supplying a low voltage current to the titanium anode rods and then periodically comparin...

Страница 9: ...or rotten egg smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any...

Страница 10: ...ing it must be installed on top of a metal or wood panel extending beyond the full width and depth of the appliance by at least three 3 inches 7 6 cm in any direction or if the appliance is to be inst...

Страница 11: ...nt position by sliding or walking 2 Place drain pan underneath water heater INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE if not already installed DANGER Temperature setting should not exceed safe tem...

Страница 12: ...ther stripping heavy insulation caulking vapor barrier etc air for combustion and ventilation must be obtained from outdoors This may be accomplished by piping air directly to the water heater from ou...

Страница 13: ...chemicals calcium and sodium chloride waxes and process chemicals are corrosive Products of this sort should not be stored near the water heater or outside by the air intake if applicable TYPICAL INS...

Страница 14: ...Three Water Heater Connection Figure 8 Typical Four Water Heater Connection This drawing shows a suggested piping configuration and other devices check with local codes and ordinances for additional...

Страница 15: ...r supply system such as the one having a back flow preventer in the cold water supply provisions must be made to control thermal expansion DO NOT operate this water heater in a closed system without p...

Страница 16: ...uses a means such as an ASSE approved mixing valve shall be installed to temper the water for those uses in order to reduce scald hazard potential Failure to properly pipe this water heater may result...

Страница 17: ...ceilings unless rubber isolation pipe hangers are used This prevents any vibrations from being transmitted into the living spaces Do not exceed the venting distances or the number of elbows listed in...

Страница 18: ...to be used within their marked time limitations For installations in the US only PVC DWV ASTM D 2665 PVC Sch 40 80 120 ASTM D1785 CPVC Sch 40 80 ASTM F441 CPVC ASTM D2846 ABS Sch 40 DWV ASTM D2661 Fo...

Страница 19: ...irculation may involve angling the intake away from the exhaust terminal increasing the distance between them relocating the air intake to another side of the building or using inside air for combusti...

Страница 20: ...located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal b b K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within...

Страница 21: ...inal 12 inches 30 cm a 12 inches 30 cm a K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet horizontally E Clearance to unventilated soffit 12 inches 30 cm...

Страница 22: ...ipe length CAUTION Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or venting system Stress levels in the pipe and fittings can be signific...

Страница 23: ...t move freely through a wall penetration the pipe may be directly stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses Follo...

Страница 24: ...he wall at a height greater than or equal to 12 30 5 cm and above expected snow level from the ground then the installation must be modified as shown below see Figure 14 Refer to Tables 3 or 4 for max...

Страница 25: ...e total length of straight vent pipe in feet required for both the intake and the exhaust 2 Add 5 feet of venting for every 90 elbow 3 Add 2 feet of venting for every 45 elbow 4 Total vent length cann...

Страница 26: ...If rigid pipe clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high thermal stresses may be formed when the...

Страница 27: ...e below to vent through the roof 1 Cut the necessary holes through the roof and ceiling Cut one 4 inch 11 5 cm diameter hole for 4 inch 10 2 cm diameter pipe or one 6 for 6 inch 15 2 cm diameter pipe...

Страница 28: ...d 2 feet of venting for every 45 elbow 4 Total vent length cannot exceed Max Vent Length in Table 4 Example of Total Vent Length for 120T400 with a power vented installation A 3 venting system has a t...

Страница 29: ...RATION DISTANCES Note When installing multiple intake exhaust terminals on the same wall of a building the nearest intake terminal must be at least 5 feet from the nearest exhaust terminal Spacing req...

Страница 30: ...rical disconnect switch is in the OFF position Electrical shock can cause personal injury or death DO NOT operate this water heater with the rain cap removed or recirculation of combustion products ma...

Страница 31: ...e the roof surface or anticipated snow level See Figure 22 If assembly is too short to meet height requirements the two pipes supplied in the kit may be replaced by using the same diameter pipe DO NOT...

Страница 32: ...ure 21 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside pipe assembly...

Страница 33: ...eck pipe and fittings for splits or cracks and replace if found b Clean pipe and fittings are imperative for proper joining Following cutting and deburring wipe away any foreign material with a clean...

Страница 34: ...p and water solution and a brush or a commercial leak detector fluid NEVER USE A MATCH OR OPEN FLAME FOR TESTING The water heater is not intended for operation at higher than 14 0 inch water column ps...

Страница 35: ...maximum 14 0 inch W C and a minimum supply pressure as shown on the rating plate The inlet gas pressure must not exceed the maximum value In some installations a regulator sized for the input rating o...

Страница 36: ...y a switch that is used to control lights or another appliance If wiring in conduit is required cut the line cord close to the control board and make the appropriate wiring connections Install an elec...

Страница 37: ...sional 1 Flooding to or above the level of the burner or controls 2 External firing 3 Damage 4 Firing without water 5 Sooting NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WI...

Страница 38: ...LIGHTING AND SHUT DOWN INSTRUCTIONS Figure 26 Lighting Instruction Label 38...

Страница 39: ...status of the water heater Idle or Heating If the water heater is functioning normally the display will also show Operational For energy efficient operation of your water heater the suggested initial...

Страница 40: ...the water temperature to the maximum set point can result in scalding hot water delivered to the faucets It is highly recommended that the maximum setpoint be adjusted to the lowest temperature possi...

Страница 41: ...Temperature Up button until desired setpoint temperature appears in the display Step 2 Press DONE button for new setting to take effect immediately If the DONE button is not pressed the new temperatur...

Страница 42: ...NE button is not pressed the new temperature setting will take effect in approximately 10 seconds NOTICE Pressing the NEXT button instead of DONE will enter the display to show unused screens such as...

Страница 43: ...To Change Temperature Format in Display from F to C or C to F Step 1 Enter Set UP Mode by pressing both UP DOWN buttons together for 3 seconds 43...

Страница 44: ...tures while shut off the water heater and piping should be fully drained See To Drain the Water Heater and the drain valve should be left fully open WARNING Hydrogen gas can be produced in an operatin...

Страница 45: ...l of lime scale The unit should be inspected and adjusted to maintain proper combustion Refer to Table 5 Suggested Maintenance Schedule A periodic inspection of the venting system should be made BURNE...

Страница 46: ...eplace as Required Relief Valve Check Operation Semi Annually Proper Operation Blower Clean Inlet Screen As Required Soft Brush Vent Air Intake System Inspect Every 3 Months Joints should be sealed Ig...

Страница 47: ...ces the hardness of the water However this equipment does not always remove all of the hardness lime For this reason it is recommended that a regular schedule of deliming be maintained The depth of th...

Страница 48: ...ll not turn off the powered anode system as long as the line cord is plugged in and the breaker is left on The powered anode control module is located on the right vertical side of the control panel i...

Страница 49: ...d In a closed system thermal expansion will cause the system pressure to build until the relief valve actuation pressure is equaled Then the relief valve will open allowing some water to escape slight...

Страница 50: ...he maximum number of ignition retries for ignition The control will make another 4 ignition attempts after the 15 minute waiting period 10 If the exhaust vent terminal should become blocked or the con...

Страница 51: ...ode for 12 5 minutes after the last button press for viewing unless Done button is pressed to exit Diagnostic Mode Step 2 The display will show the flame sense current in microamps when the burner is...

Страница 52: ...button and the display will show the temperature sensor reading Step 6 Press lower right Next button and the display will show the manual firing rate adjustment This function is not currently used Any...

Страница 53: ...ower supply and make sure that frequency voltage and VA capacity of the transformer meet specifications Check to make sure the wiring connections on the control module from terminals J4 10 and J8 2 ar...

Страница 54: ...ion ground wires If problem persists and all other checks have been verified replace the control module 110 Ignition Failure Occurred Burner failed to light or stay lit after 3 retries Hold condition...

Страница 55: ...592 11308 11032 10763 10502 10248 10000 9760 9526 80 9299 9078 8862 8653 8449 8250 8057 7869 7685 7507 90 7333 7165 7000 6839 6683 6531 6383 6238 6098 5961 100 5827 5697 5570 5446 5326 5208 5094 4982...

Страница 56: ...anout Access Cover 18 Cleanout Gasket 19 Cold Water Inlet Hydrojet Assembly 20 Exhaust Pressure Switch 21 Pressure Switch Cover 22 Exhaust Limit Switch 23 Service Door Right 24 Exhaust Coupler 25 Cond...

Страница 57: ...400 Hex Nut 120T500 9 Transition Tube Specify Model 10 Screw 11 Spark Rod 12 Spark Rod Gasket 13 Flame Sensor 14 Flame Sensor Gasket 15 Hex Nut 16 Burner Gasket Specify Model 17 Burner Specify Model 1...

Страница 58: ...atent applications pending Current Canadian Patents 2 092 105 2 107 012 2 108 186 2 112 515 2 143 031 2 239 007 2 262 174 2 314 845 2 409 271 2 476 685 2 504 824 2 548 958 CC Ignition Control Assembly...

Страница 59: ...NOTES 59...

Страница 60: ...ite com Warranty 800 531 2111 Email warranty bradfordwhite com Service Parts 800 538 2020 Email Parts bradfordwhite com International international bradfordwhite com Halton Hills ON Sales Technical Su...

Отзывы: