This water heater has a certified category IV, per latest ANSI Z 21.10.3-2017.CSA 4.3-2017 revision. Refer to
the latest edition of the National Fuel Gas Code (ANSI Z223.1-latest edition), or in Canada, the Natural Gas and
Propane installation Code (B149.1-00 latest edition).
NOTICE
For installations in Canada, field supplied vent piping must comply with CAN/CGA B149.1 (latest edition) and be
certified to the Standard For Type BH, Class II, 65°C, Gas Venting Systems, ULC S636. Components of this listed
system shall not be interchanged with other vent systems or unlisted pipe/fittings. All components and specified
primers and cements of the certified vent system must be from a single system manufacturer and not intermixed with
other system manufacturer’s vent system parts. The supplied vent connector and vent termination are certified under
ULC S636 and are also certified as part of the water heater. Refer to the following tables for approved venting
materials, primers, and cements. All approved primers and cements are to be used within their marked time
limitations.
For installations in the US only
PVC DWV (ASTM D-2665)
PVC Sch. 40, 80, 120 (ASTM-D1785)
CPVC Sch. 40, 80 (ASTM-F441)
CPVC (ASTM D2846)
ABS Sch. 40 DWV (ASTM D2661)
For installations in CANADA
ULC S636 approved PVC for flue gas
venting rated Class II, 65°C
ULC S636 approved CPVC for flue gas
venting rated Class II, 65°C
For installations in the US only
PVC and CPVC Primer (ASTM-F656)
PVC Cement (ASTM D-2564)
CPVC Cement (ASTM F493)
ABS Primer and Cement (ASTM D-
2235)
For installations in CANADA
ULC S636 approved Primer and
Cement for flue gas venting rated
Class II, 65°C
NOTICE
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel
®
(polyphenosulfone) in non-metallic venting systems is prohibited and
covering non-metallic venting with thermal insulation is prohibited.
NOTICE
Before beginning installation of any vent pipe, read the vent pipe manufacturer’s installation instructions.
Do not install the water heater in any location where the ambient temperature may fall below freezing. Water heater
must be protected from freezing downdrafts during shutdown periods.
Provide protection of the building materials from degradation by flue gases from the exhaust vent terminal.