1.3 Approved Use
BOWMAN
®
"Exhaust Gas Heat Exchangers" are only approved for reclaiming heat from
waste exhaust gases.
Any other use unless specified by
BOWMAN
®
is not approved.
BOWMAN
®
declines all
liability for damage associated or arising from such use.
The maximum permissible operating pressures must not exceed:
Gas (tube side)
:
0.5 bar max.
Water (shell side)
:
4.0 bar max.
The maximum permissible operating temperature must not exceed:
Gas (tube side)
:
700°C
Water (shell side)
:
110°C
European Pressure Equipment Directive
This range of products fall within within Article 3 Paragraph 3
(Sound Engineering Practice) and do not require CE marking.
1.4 Potential Hazards
The heat exchanger may be damaged or leak if the maximum permissible
operating
pressure is exceeded.
Connections on the exhaust gas side of the heat exchanger may reach temperatures as high
as 700°C
Connections on the cooling water side of the heat exchanger may reach temperatures as
high as 110°C
1.5 Safety Measures at Installation Site
The heat exchanger should not be used without sufficient cooling water flow through the shell
side.
Ensure the maximum permissible operating pressure on the primary or secondary side
of the heat exchanger is not exceeded. The heat exchanger or surrounding equipment
may be damaged.
While the system is in operation, weekly inspection of the heat exchanger and its
connections should be maintained for leaks and externally visible damage.