7   Performance 

Typical examples of exhaust gas heat exchanger performance.  The figures below are a general 
guide  only  and  are  not  based  on  any  particular  natural  gas  engine.    They  assume  an  air/fuel 
ratio  of  10.23  :  1  by  volume,  a  fuel  consumption  of  0.34m

3

/kWh  (measured  at  1.013  bar  and 

15°C) and an exhaust gas temperature of 600°C and a water temperature of 80°C. 
Figures are based on new and clean conditions. 

 

 

 

 E.J. Bowman (Birmingham) Ltd, reserve the right to change specification and technical alteration without prior notice. 

Type 

Typical            

Engine Power                 

kW 

Exhaust Gas Flow 

kg/min 

Exhaust Gas 

Outlet Temp         

°C 

Heat Recovery    

kW 

Exhaust Gas 

Pressure Drop       

kPa 

2-25-3737-4 

16 

1.2 

210 

9.5 

1.6 

2-32-3737-5 

16 

1.2 

170 

11.5 

1.8 

3-32-3738-5 

32 

2.4 

210 

19 

1.5 

3-40-3738-6 

32 

2.4 

170 

21 

1.7 

3-60-3738-8 

32 

2.4 

120 

23 

2.2 

4-32-3739-5 

60 

4.5 

210 

35 

1.3 

4-40-3739-6 

60 

4.5 

170 

39 

1.4 

4-60-3739-8 

60 

4.5 

120 

43 

1.8 

5-32-3740-5 

90 

6.7 

210 

53 

1.2 

5-40-3739-6 

60 

4.5 

170 

39 

1.4 

5-60-3740-8 

90 

6.7 

120 

65 

1.8 

6-32-3741-5 

140 

10.5 

210 

82 

1.3 

6-40-3741-6 

140 

10.5 

170 

90 

1.4 

6-60-3741-8 

140 

10.5 

120 

101 

1.9 

8-32-3742-5 

250 

18.7 

210 

147 

1.3 

8-40-3742-6 

250 

18.7 

170 

161 

1.4 

8-60-3742-8 

250 

18.7 

120 

181 

1.8 

10-32-3744-5 

400 

30 

210 

236 

1.3 

10-40-3743-6 

400 

30 

170 

256 

1.4 

10-60-3743-8 

400 

30 

120 

288 

1.8 

12-32-3744-5 

600 

45 

210 

353 

1.3 

12-40-3744-6 

600 

45 

170 

388 

1.5 

12-60-3744-8 

600 

45 

120 

425 

1.9 

15-40-5745-6 

950 

70 

170 

604 

1.4 

15-60-5745-8 

950 

70 

120 

670 

1.9 

Содержание 10-32-3744-5

Страница 1: ...EXHAUST GAS HEAT EXCHANGERS Installation Operation Maintenance Guide REG NO FM 38224 BS EN ISO 9001 2008 ...

Страница 2: ...eep the Installation Operation Maintenance Guide for all future reference to ensure the long lasting performance from your Exhaust Gas Heat Exchanger All rights reserved E J Bowman Birmingham Ltd reserve the right to change specification and technical alteration without prior notice No part of this guide may be reproduced or transmitted in any form or by any means including reproduction or recordi...

Страница 3: ... T A L L A T I O N 2 1 Transport storage 6 2 2 Installation 6 2 3 Connecting the heat exchanger 7 3 O P E R A T I O N 7 4 C O M M I S S I O N I N G 7 5 M A I N T E N A N C E R E P A I R 5 1 General Maintenance 8 5 2 Exhaust Gas Heat Exchanger Cleaning 8 6 W A R R A N T Y 8 7 P E R F O R M A N C E 9 8 S P A R E P A R T S L I S T 1 0 E J Bowman Birmingham Ltd Chester Street Birmingham B6 4AP United ...

Страница 4: ...only be used for its intended use In the event of breakdowns which may compromise safety a qualified technician must always be contacted 1 2 Safety Instructions The following symbols are used in these operating instructions This symbol indicates an immediate danger to health Failure to comply with this instruction may result in severe injury This symbol indicates a possible danger to health Failur...

Страница 5: ...rking 1 4 Potential Hazards The heat exchanger may be damaged or leak if the maximum permissible operating pressure is exceeded Connections on the exhaust gas side of the heat exchanger may reach temperatures as high as 700 C Connections on the cooling water side of the heat exchanger may reach temperatures as high as 110 C 1 5 Safety Measures at Installation Site The heat exchanger should not be ...

Страница 6: ...dary circuit is fully vented via the vent plug fitted in order to prevent any aeration taking place which can cause erosion of the tubes c If ethylene glycol or any other heat transfer fluid is used in the secondary circuit adequate mixing should be performed prior to filling of the heat exchanger d If temperature control sensors are fitted to either the primary or secondary circuits of the heat e...

Страница 7: ...ircuit pumps are in continual operation whenever the primary circuit is in operation c Provision should also be made to ensure that any valves or ancillary equipment associated with either the primary or secondary side of the heat exchanger cannot be accidentally turned off thereby preventing flow through the heat exchanger d It is very important that the secondary circuit is fully vented via the ...

Страница 8: ...vailable from companies such as Easy Products www easyproductsltd com d Detergents or chemicals suitable for use with stainless steels can be used if fouling is severe Allow time for the detergent or chemical cleaner to work before hosing down with plenty of water e The tube stack should be flushed through with clean water to remove all traces of cleaning chemicals detergents If necessary the clea...

Страница 9: ...very kW Exhaust Gas Pressure Drop kPa 2 25 3737 4 16 1 2 210 9 5 1 6 2 32 3737 5 16 1 2 170 11 5 1 8 3 32 3738 5 32 2 4 210 19 1 5 3 40 3738 6 32 2 4 170 21 1 7 3 60 3738 8 32 2 4 120 23 2 2 4 32 3739 5 60 4 5 210 35 1 3 4 40 3739 6 60 4 5 170 39 1 4 4 60 3739 8 60 4 5 120 43 1 8 5 32 3740 5 90 6 7 210 53 1 2 5 40 3739 6 60 4 5 170 39 1 4 5 60 3740 8 90 6 7 120 65 1 8 6 32 3741 5 140 10 5 210 82 1...

Страница 10: ...3862 15 5745 EX043 5757CI EX044 5758CI 3795 4484 5759 Type Inlet End Cover A Outlet End Cover B Pressure Relief Valve C Mounting Foot D End Cover Gasket E 2 5837 EX062 5334CI EX062 5334CI 4028 4476 3787 3 5838 EX063 5335CI EX063 5335CI 4028 4477 3788 4 5839 EX064 5336CI EX064 5336CI 4028 4478 3789 5 5840 EX065 5337CI EX065 5337CI 3795 4479 3790 6 5841 EX066 4982CI EX066 4982CI 3795 4480 3791 8 584...

Страница 11: ...ineTestHouseCooling MiningIndustry MarineCooling SwimmingPool SpaIndustry FishingIndustryCooling The product range includes MarineHeatExchangers HeaderTankHeatExchangers SwimmingPoolHeatExchangers ChargeAirCoolers StainlessSteelHeatExchangers InlinePlateTypeHeatExchangers FuelCoolers Shell TubeHeatExchangers TitaniumHeatExchangers Aftercoolers AquaticHeatExchangers Non StorageCalorifiers ...

Отзывы: