Solution 64 | Installer Guide | Input Programming
7-10
Bosch Security Systems | 11/05 | BLCC110I
Global Input Options
Inputs > Global Input Options >
EOL Value
MENU 3-4-0
0 = No EOL
5
1 = 1K0
6 = 4K7
11 = 12K
2 = 1K5
7 = 5K6
12 = 15K
3 = 2K2
8 = 6K8
13 = 22K
4 = 2K7
9 = 8K1
14 = 3K3 with Tamper (6K8)
5 = 3K3
10 = 10K
15 = Split EOL (Parallel)
(3K3 = Primary, 6K8 = Secondary)
This menu programs the End Of Line resistor (EOL) value that
is global for all hard-wired zones including zones on the Zone
Expander Module. Only one EOL Value can be programmed.
Setting the EOL Value to type 0 to 14 will configure the system
as 8 hardwired zones and 16 on the expander board if one is
fitted. Setting the option to type 15 will configure the main
panel as 16 HW zones and the optional expander board as 32
HW zones.
Press [MENU] + [3] + [4] + [0]. The keypad will display the
current EOL value (Default = 5).
EOL Value
05 - 3k3 Ohm
Press
0-9 OK to Save
Use the up and down arrows to select the EOL Value you want
to use then press [OK] to save and exit or press [MENU] to exit
without saving.
Inputs > Global Input Options >
Keyswitch Options
MENU 3-4-1
0
= Latching - All On/Off
5 =
Momentary All On/Off
0
1 =
Latching - All On
6 =
Momentary - All On
2 =
Latching Part On/Off
7 =
Momentary - Part
On/Off
3 =
Latching - Part On
8 =
Momentary - Part On
4 =
Latching Off
9 =
Momentary - Off
(*** System Wide Parameter ***)
This menu programs the properties for any zone in the system
programmed as a keyswitch zone. Only one option can be
selected for the entire system which means that all keyswitches
fitted will behave the same way.
The system can send Open and Close reports based on the
keyswitch operation with the zone number representing the
user number in the report.
Press [MENU] + [3] + [4] + [1]. The keypad will display the
current keyswitch options (Default = 0 Disabled).
Keyswitch Options
00 - Latching All On/Off
Press
0-9 OK to Save
1)
2)
1)
Use the up and down arrows to select the required keyswitch
option then press [OK] to save and exit or press [MENU] to exit
without saving.
Inputs > Global Input Options >
Input Options
MENU 3-4-2
1
Tamper On Short
N
2
Reserved
N
3
Response Time 500ms
N
4
Reserved
N
5
Reserved
N
6
Reserved
N
7
Reserved
N
8
Reserved
N
(*** System Wide Parameter ***)
This menu programs the various global input options which will effect
all zones on the system.
Tamper On Short
Setting this option will cause any Zone which become shorted to
report a tamper alarm condition for the zone.
Response Time 500ms
Setting this option will increase the response time for all zones to
500ms.
Inputs > PGM Input >
Input Type
MENU 3-5-0
0
0 =
Disabled
1 =
Latching - On/Off (RF Relay)
5 =
Crow Serial RF Receiver
2 =
Momentary - On/Off (RF Relay)
6 =
Ness Serial RF Receiver
3 =
Bosch RF On/Off
7 =
Inovonics Serial RF RX
4 =
DS Serial RF Receiver
8 =
Secure Wireless RF RX
This menu option is used to configure the systems
programmable input terminal. Various devices can be
connected including keyswitches of radio controlled relays
etc. When RF zones are required you need to connect the RF
receiver to this input
Connect keyswitch between Input terminal and GND. See
Wiring Diagrams in Section 3 for various connection diagrams.
Press [MENU] + [3] + [5] + [0]. The keypad will display the
current input type (Default = 0 Disabled).
Input Type P001
00 - Disabled
Press
0-9 OK to Save
Use the up and down arrows to select the required Input
Device Type then press [OK] to save and exit or press [MENU] to
exit without saving.
i
Note
The Latching and Momentary On/Off modes are active low, and
when triggered, they will automatically force arm the area.
2)
1)
2)