REFUspeed RS51
Basic parameterization
7-13
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0890
Ref., analogue output Reference, analogue output
+10V reference
output
1
0 = +10V reference output
1 = -10V reference output
2 = fact output frequency
3 = Iact output current (apparent current)
4 = Isq torque-generating (active current)
5 = Vact output voltage
6 = Pact output power
7 = Pactive active power
0...7
0221.00
PT1 filt. timeconst
Supplementary parameter for “analog output”.
0 ms
1
To smooth any value which is connected at the analog
output.
0 ... 10000 ms
0559
Pactual PT1 time
Supplementary parameter for “analog output”.
50 ms
1
Only to smooth the Pact value.
0 ... 10000 ms
0560
Ptrue PT1 filter time
Supplementary parameter for “analog output”.
50 ms
1
Only to smooth the Pactive value.
0 ... 10000 ms
0411
Output-block signal
Supplementary parameter for “analog output”.
Direct
1
Defines how a signal is transferred.
0 = direct
1 = absolute value
2 = inverted
3 = absolute value, inverted
0...3
0413
Output-block, norm.
Supplementary parameter for “analog output”.
100.00 %
1
Normalization of the analog output 10 V correspond to
the value set here.
6.26 ... 200.00 %
0561
Output-block
Supplementary parameter for “analog output”.
0.. ±100 %
2
0 = 0 ... ±100 %
1 = + 20 ... +100 %
0 / 1
0412
Output-block offs.
Supplementary parameter for “analog output”.
0.00 %
1
Offset
-100.00 ... 100.00
%
Functions
•
Controller setting
•
Start/stop function
•
Thermal motor protection
•
V/Hz control (open loop)
•
Active load monitor
•
Additional functions