REFUspeed RS51
Electrical installation
5-15
DOK-RD500*-RS51*******-IB02-EN-P
Terminal
Designation
Comment
X13
SS6
Only for internal use
X14
Standard terminal strip
1
P24V output
Load capacity, max. 50 mA
2
Dig. input 1
Dig. output 1
Optional, input / output; func-
tion can be selected using
P0875
3
Dig. input 2
Dig. output 2
Optional, input / output; func-
tion can be selected using
P876
4
Dig. input 3
Dig. output 3
Optional, input / output; func-
tion can be selected using
P0877
5
Dig. input 4
Function can be selected using
P0878
6
Dig. input 5
Digital inputs without electrical isolation:
Input current at 24 V: 8.6 mA
H signal: +13 V ... +33 V
L signal: –3 V ... +5V or
open terminal
Digital outputs
H signal: +21 V, max. 20 mA
L signal: 0 V
Function can be selected using
P0879
7
Digital ground
Reference ground of the P24V (X14.1)
if the digital inputs are switched from a control system, the ground cable from
X14.7 to the ground reference point must be removed.
8
Reference ±10 V
Analog output
Optional function, can be switched-over using P0890
(5 mA load capacity, short-circuit proof):
Reference v10 V
Reference voltage –10 V
Analog output 0 ... ±10 V
9
Analog input+
10
Analog input -
Differential input can be optionally selected:
±10 V;
A/D converter ±9 bit;
resolution 20 mV, R
e
= 40 k
Ω
0 ... 20 mA;
A/D converter 10 bit;
resolution 0.02 mA, R
e
= 150
Ω
4 ... 20 mA;
A/D converter 10 bit;
resolution 0.02 mA, R
e
= 150
Ω
11
Analog ground
Reference ground of the reference voltage or the analog output (X14.8)
X15
Motor temperature sensor
1
PTC+ / KTY+
2
PTC- / KTY -
Motor temperature sensor connection (PTC or KTY84). Observe the polarity
when connecting a KTY84!
X16
Relay output
1
NO contact
2
Common
contact
Dig. input
9
NC contact
Relay output
Load capacity:
250 V AC, 7 A
30 V DC, 7 A
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01