REFUspeed RS51
Basic parameterization
7-23
DOK-RD500*-RS51*******-IB02-EN-P
Serial communications
Sub-menu to set standard RS485 interfaces.
Parame-
ter No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0500
SI1 protocol X12
The serial interface 1 (SS1) is an RS485 interface
(connection X12).
0
=
No protocol
1
=
USS 4/2 words
2
=
USS 4/6 words
3
=
USS 0/2 words
4
=
USS 0/6 words
5
=
USS 4/0 words
USS 4/6 words
0 ... 5
2
0501
SI1 baud rate X12
0
=
1200 baud
1
=
2400 baud
2
=
4800 baud
3
=
9600 baud
4
=
19200 baud
5
=
38400 baud
6
=
76800 baud
9600 baud
0 ... 6
2
0502
SI1 parity
X12
0
=
No parity
1
=
ODD
2
=
EVEN
Even
0 ... 2
2
0503
SI1 stop bits
X12
1 or 2 stop bits can be set.
1
1 ... 2
2
0504
SI1 slave address
The drive converter address can be set between 0 and
31 for the RS485 bus. Caution: There must be no two
identical addresses on the bus (each station/node
must have ist own unique address)!
0
0 ... 31
2
0505
SI1 Rx watchdog
0
=
No reaction
1
=
Warning
2
=
Fault
Fault
0 ... 2
2
0506
SI1 Rx timeout
Timeout (monitoring) time for the standard SS1 inter-
face. If this interface does not receive an error-free
protocol within this time, then the response, selected
in P0505 is initiated.
0.1 s
0.1 ... 60.0 s
2