Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
21
3.3.4 Environmental installation conditions
The air is classified by the EN 60721-3-3 standard (Classification of environmental
parameters and their severities – Stationary use at weather-protected locations) based on
climatic and biological conditions as well as on mechanically and chemically active substances.
Therefore the place of installation must meet specific requirements to ensure compliance
with the conditions for which the UPS was designed.
Climatic conditions according to the technical specification of B9000FXS
Environmental parameter
Minimum operating temperature (°C)
– 10
Maximum operating temperature (°C)
+ 40
Minimum relative humidity (%)
5
Maximum relative humidity (%)
95
Condensation
NO
Rainfall with wind (rain, snow, hail, etc.)
NO
Water with an origin other than rain
NO
Ice formation
NO
Classification of biological conditions (EN 60721-3-3)
Environmental
parameter
Class
3B1
3B2
3B3
a)
Flora
NO
Presence of mildew, fungus,
etc.
Presence of mildew, fungus,
etc.
b)
Fauna
NO
Presence of rodents and
other animals that are
harmful to products,
excluding termites
Presence of rodents and
other animals that are
harmful to products,
including termites
Classification of mechanically active substances (EN 60721-3-3)
Environmental parameter
Class
3S1
3S2
3S3
3S4
a)
Sand [mg/m
3
]
No
30 300
3000
b)
Dust (suspension) [mg/m
3
]
0,01 0,2 0,4 4,0
c)
Dust (sedimentation) [mg/(m
2
·h)
0,4 1,5 15 40
Places where precautions have been taken to minimize the presence
of dust. Places away from dust sources
X
Places without any special precaution to minimize the presence of
sand or dust, however not in proximity to sand or dust sources
X
Places in proximity to sand or dust sources
X
Places in proximity to working processes that generate sand or dust,
or in geographic areas having a high proportion of sand brought by
the wind or of dust suspended in the air
X
Содержание ASD10
Страница 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Страница 2: ......
Страница 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Страница 6: ...Warnings and general information Avvertenze e informazioni generali OMD10080 REV B 3 ENGLISH LANGUAGE ...
Страница 12: ...Warnings and general information Avvertenze e informazioni generali OMD10080 REV B 9 LINGUA ITALIANA ...
Страница 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Страница 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...