Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
18
OMD10081 REV. I
3.3.1 Base plan, static load and weights
Picture 3 – Base plan
Power (kVA)
60 80 100 125 160
L1 (mm)
815
P1 (mm)
825
L2 (mm)
70
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its
steady and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Power (kVA)
60 80 100 125 160
Weight (kg)
570
600
630
662
720
Static load (kg/m
2
) 948
998
1048
1101
1198